Electrical Control Function
Electrical Control System
115
1.3.9 Drain pump control (For cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling), dehumidifying, and forced cooling mode, the
pump will start running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes,
1.3.10 Point Check Function (Excluding 12K &18K)
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Norm code *HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temp.(Cooling:T2,
heating:T2B)
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube will
show “-9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected,
the digital display tube will show: “――”
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(Tp)
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show “13”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show “0.5”,it means the compressor discharge
temp. is 105 degree. the digital display tube show “1.6”,it
means the compressor discharge temp. is 116 degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
Содержание LISAS-B-1403
Страница 10: ...Features 12K 18K 8 Indoor Units ...
Страница 15: ...Features 24K 36K Indoor Units 13 ...
Страница 18: ...Service Space 16 Indoor Units 4 Service Space ...
Страница 31: ...Wiring Diagrams Indoor Units 29 ...
Страница 45: ...Service Space Indoor Units 43 3 Service Space 12K 18K C Ý 3 5mm Ý 3 5mm Ý 35mm Ý 1000mm 24K 48K ...
Страница 46: ...Wiring Diagrams 44 Indoor Units 4 Wiring Diagrams UB012GMFI16MLD UB018GMFI16MLD ...
Страница 47: ...Wiring Diagrams Indoor Units 45 UB024GMFI16MLD UB036GMFI16MLD UB048GMFI16MLD ...
Страница 52: ......
Страница 55: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 56: ...Service Space 54 Indoor Units 3 Service Space ...
Страница 57: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams FB012GMFI16MLD ...
Страница 61: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M ...
Страница 64: ...Dimensions 62 Outdoor Units Model Unit mm A B C D E F H YN048GMFI16RUD 938 634 404 448 370 392 1369 ...
Страница 67: ...Wiring Diagrams Outdoor Units 65 4 Wiring Diagrams YN012GMFI16RUD YN018GMFI16RUD ...
Страница 68: ...Wiring Diagrams 66 Outdoor Units YN024GMFI16RUD ...
Страница 69: ...Wiring Diagrams Outdoor Units 67 YN036GMFI16RUD YN048GMFI16RUD ...
Страница 125: ...Troubleshooting Electrical Control System 123 2 4 1 2 Outdoor unit malfunction ...
Страница 130: ...Troubleshooting 128 Electrical Control System 2 4 4 For the outdoor unit 2 4 4 2 E0 malfunction ...
Страница 131: ...Troubleshooting Electrical Control System 129 2 4 4 3 E2 malfunction Only for 12 18K ...
Страница 132: ...Troubleshooting 130 Electrical Control System 2 4 4 4 E2 malfunction For 24 48K ...
Страница 133: ...Troubleshooting Electrical Control System 131 2 4 4 5 E3 malfunction ...
Страница 134: ...Troubleshooting 132 Electrical Control System 2 4 4 6 E4 malfunction ...
Страница 136: ...Troubleshooting 134 Electrical Control System 2 4 4 8 E6 malfunction Only for 36K 48K ...
Страница 138: ...Troubleshooting 136 Electrical Control System 2 4 4 10 P1 malfunction Only for 36K 48K ...
Страница 139: ...Troubleshooting Electrical Control System 137 2 4 4 11 P2 malfunction Only for 36K 48K ...
Страница 140: ...Troubleshooting 138 Electrical Control System 2 4 4 12 P3 malfunction ...