Vacuum Drying and Leakage Checking
98
Installation
7 Vacuum Drying and Leakage Checking
7.1 Purpose of vacuum drying
Eliminating moisture in system to prevent the phenomena of ice-blockage and copper oxidation.
Ice-blockage shall cause abnormal operation of system, while copper oxide shall damage compressor.
Eliminating the non-condensable gas (air) in system to prevent the components oxidizing, pressure
fluctuation and bad heat exchange during the operation of system.
7.2 Selection of vacuum pump
The ultimate vacuum degree of vacuum pump shall be -756mmHg or above.
Precision of vacuum pump shall reach 0.02mmHg or above.
7.3 Operation procedure for vacuum drying
Due to different construction environment, two kinds of vacuum drying ways could be chosen, namely
ordinary vacuum drying and special vacuum drying.
7.3.1 Ordinary vacuum drying
1. When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid
pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached
-755mmHg).
2 If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates
that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
3 If the vacuum degree of vacuum pump still could not reach -755mmHg after 1.5 hours of drying, check
whether there is leakage source.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
7.3.2 Special vacuum drying
The special vacuum drying method shall be adopted when:
1. Finding moisture during flushing refrigerant pipe.
2. Conducting construction on rainy day, because rain water might penetrated into pipeline.
3. Construction period is long, and rain water might penetrated into pipeline.
4. Rain water might penetrate into pipeline during construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this
method could not achieve drying thoroughly when there is too much moisture. Therefore, special
attention shall be drawn to prevent the entering of water and the formation of condensate water.
3. Vacuum drying again for half an hour.
If the pressure reaches -755mmHg, start to pressure leakage test. If it cannot reach the value, repeat
vacuum damage and vacuum drying again for 1 hour.
4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
Содержание LISAS-B-1403
Страница 10: ...Features 12K 18K 8 Indoor Units ...
Страница 15: ...Features 24K 36K Indoor Units 13 ...
Страница 18: ...Service Space 16 Indoor Units 4 Service Space ...
Страница 31: ...Wiring Diagrams Indoor Units 29 ...
Страница 45: ...Service Space Indoor Units 43 3 Service Space 12K 18K C Ý 3 5mm Ý 3 5mm Ý 35mm Ý 1000mm 24K 48K ...
Страница 46: ...Wiring Diagrams 44 Indoor Units 4 Wiring Diagrams UB012GMFI16MLD UB018GMFI16MLD ...
Страница 47: ...Wiring Diagrams Indoor Units 45 UB024GMFI16MLD UB036GMFI16MLD UB048GMFI16MLD ...
Страница 52: ......
Страница 55: ...Dimensions Indoor Units 53 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 56: ...Service Space 54 Indoor Units 3 Service Space ...
Страница 57: ...Wiring Diagrams Indoor Units 55 4 Wiring Diagrams FB012GMFI16MLD ...
Страница 61: ...Field Wiring Indoor Units 59 9 Field Wiring MFAU 12HRFN1 M ...
Страница 64: ...Dimensions 62 Outdoor Units Model Unit mm A B C D E F H YN048GMFI16RUD 938 634 404 448 370 392 1369 ...
Страница 67: ...Wiring Diagrams Outdoor Units 65 4 Wiring Diagrams YN012GMFI16RUD YN018GMFI16RUD ...
Страница 68: ...Wiring Diagrams 66 Outdoor Units YN024GMFI16RUD ...
Страница 69: ...Wiring Diagrams Outdoor Units 67 YN036GMFI16RUD YN048GMFI16RUD ...
Страница 125: ...Troubleshooting Electrical Control System 123 2 4 1 2 Outdoor unit malfunction ...
Страница 130: ...Troubleshooting 128 Electrical Control System 2 4 4 For the outdoor unit 2 4 4 2 E0 malfunction ...
Страница 131: ...Troubleshooting Electrical Control System 129 2 4 4 3 E2 malfunction Only for 12 18K ...
Страница 132: ...Troubleshooting 130 Electrical Control System 2 4 4 4 E2 malfunction For 24 48K ...
Страница 133: ...Troubleshooting Electrical Control System 131 2 4 4 5 E3 malfunction ...
Страница 134: ...Troubleshooting 132 Electrical Control System 2 4 4 6 E4 malfunction ...
Страница 136: ...Troubleshooting 134 Electrical Control System 2 4 4 8 E6 malfunction Only for 36K 48K ...
Страница 138: ...Troubleshooting 136 Electrical Control System 2 4 4 10 P1 malfunction Only for 36K 48K ...
Страница 139: ...Troubleshooting Electrical Control System 137 2 4 4 11 P2 malfunction Only for 36K 48K ...
Страница 140: ...Troubleshooting 138 Electrical Control System 2 4 4 12 P3 malfunction ...