Controller Operation
Controller Operation
2.4.8 Temperature Browsing
In normal operation, press <DISPLAY> button to enter into temperature browsing menu. Press
<SELECT
▲
/
▼
> button to select the menu as follow:
Menu
Shown in error code
display section
Value
Shown clock display section Unit
Remarks
C0
Main board DIP switch setting unit
C1
Indoor coil 1 temperature
C2
Indoor coil 2 temperature
C3
Indoor coil 3 temperature
If main board is configured as dual
circuits, C3 and C4 can not be selected.
C4
Indoor coil 4 temperature
If main board is configured as three
circuits, C4 can not be selected.
Press < DISPLAY> button again to exit.
2.4.9 Keylock
System is equipped with keylock function to prevent mischief. Press
and
buttons for
5 sec to activate keylock mode. Keylock symbol will light up, likewise to exit keylock mode.
Only
button will be responded in keylock mode.
2.4.10 Key Validity
There are some buttons that will be acknowledged in certain function only. The valid key press
will be responded with the beeping sound.
2.4.11 Parameter Setting
In normal mode, press < SET> button for 5 sec to enter into parameter setting menu. Press
<SELECT
▲
/
▼
> button the select the menu. Press
or
button to edit the parameter as
follow:
Menu
Shown in error code
display section
Parameter
Shown clock display section
Characteristic Remarks
d0
d4
d5
d6
Recover to the state
before power failure.
Display as En: Recover
Display as Dn: Not recover
d1
Service password 1
0~99, default 0
d2
Service password 2
0~99, default 0
d3
Indoor coil anti freeze
-10~2degC, default 0degC
Shows number of outdoor unit
connected
C
C
C
C
Compressor consecutive
cut in interval
3~8 min, default 5min
Thermostatic control cycle
30~240 sec, default 90 sec
Recover to default setting
Display as En: Recover
Display as Dn: Not recover