No. Terminal
Description/Connected accessories
19 Backup battery
Detachable connector for rechargeable lead-acid back up battery.
The contacts are: Red: (+), Black (-)
See the next section for jump-starting with a battery.
Make sure you connect the battery wires by their
proper polarity!
20 AC
Detachable connector for AC transformer.
21 JP6
Sirens’ power source jumper - unregulated or battery.
22 JP11
EOL resistor loops jumper.
Current limit thermal fuses
F1: Detectors (750mA)
F2, F3: Siren #1 and #2 (0.9A)
F4: Keypads (750mA)
F7: Battery charger protection (200mA)
F5: PCB and battery high current Thermo-fuse (5A/250VAC) protection
F6: PCB AC short thermo-fuse (3.15A/250V) protection.
1.3.
Battery jump-start
Starting PCB version 3610100 Rev. E., during AC fault, if the backup Battery’s voltage drops under
8V, the control panel disconnects it to prevent full battery discharge. This feature extends the
battery life cycle.
Because of this, the control panel cannot be powered up using only the battery, and must be
connected to AC voltage first.
When AC voltage is not available, do the following:
a)
Connect the control panel to the Battery.
b)
Shortly connect the battery’s (-) terminal to the control
panel’s (-) terminal.
c)
The control panel will now power up.
+
-
7A
Backup
battery
Short wire
(-)