Technical Details
Operating Manual PSSu K F INC
1001688-EN-09
32
Environmental data
Climatic suitability
EN 60068-2-1, EN 60068-2-14, EN 60068-2-2, EN
60068-2-30, EN 60068-2-78
Ambient temperature
In accordance with the standard
EN 60068-2-14
Temperature range
0 - 60 °C
Storage temperature
In accordance with the standard
EN 60068-2-1/-2
Temperature range
-25 - 70 °C
Climatic suitability
In accordance with the standard
EN 60068-2-30, EN 60068-2-78
Humidity
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Max. operating height above sea level
2000 m
EMC
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
61000-4-5, EN 61000-4-6, EN 61000-6-2, EN
61000-6-4
Vibration
In accordance with the standard
EN 60068-2-6
Frequency
10 - 150 Hz, 10 - 55 Hz
Amplitude
0,35 mm
Acceleration
1g
Shock stress
In accordance with the standard
EN 60068-2-27
Number of shocks
6
Acceleration
15g
Duration
11 ms
In accordance with the standard
EN 60068-2-27
Number of shocks
1000
Acceleration
10g
Duration
16 ms
Airgap creepage
In accordance with the standard
IEC 60664-1
Overvoltage category
II
Pollution degree
2
Protection type
In accordance with the standard
EN 60529
Housing
IP20
Mounting area (e.g. control cabinet)
IP54
Mechanical data
Material
Bottom
PC
Top
PC
Connection type
D-Sub female connector, D-Sub male connector