Function description
Operating Manual PSSu K F INC
1001688-EN-09
20
The
Double evaluation
and
Quadruple evaluation
option may not be used for failsafe ap-
plications.
4.3
Configuration
4.3.1
Operating modes and parameters
The module has the following configuration options:
Configuration
Default
value
Meaning
Operating mode
X
Incremental encoder mode
Counter mode
Period length measure-
ment or latch function
X
Latch function
Period length measurement
Multiple evaluation
X
Single evaluation
Double evaluation
(2)
Quadruple evaluation
(2)
Status input
X
The status at input S is transmitted via a bit.
The status is transmitted via two redundant bits.
The status is transmitted via two diverse bits.
(1)
(1)
Transmitting the status via two bits enables simple fault detection: Two redundant bits
must always be the same, two diverse bits must always be different, otherwise the trans-
mission is faulty.
(2)
The
Double evaluation
and
Quadruple evaluation
options may not be used for failsafe
applications.