background image

PSSu E PD(-T)

Operating instructions 21304-EN-04

}

Decentralised system PSSuniversal I/O

Содержание PSSu E PD

Страница 1: ...PSSu E PD T Operating instructions 21304 EN 04 Decentralised system PSSuniversal I O...

Страница 2: ...KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET...

Страница 3: ...le features 12 4 2 1 Functions 12 4 3 Configuration 12 4 3 1 Addresses in the process image 12 Section 5 Installation 13 5 1 General installation guidelines 13 5 1 1 Dimensions 13 5 2 Installing the b...

Страница 4: ...Contents Operating instructions PSSu E PD T 21304 EN 04 4 Section 9 Order reference 25 9 1 Product 25 9 2 Accessories 25...

Страница 5: ...f symbols Information that is particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and...

Страница 6: ...Introduction Operating instructions PSSu E PD T 21304 EN 04 6 INFORMATION This gives advice on applications and provides information on special fea tures...

Страница 7: ...field wiring The electronic modules are inserted on to the base modules and determine the module s function Details of the base modules that can be used are available in the chapter entitled Intended...

Страница 8: ...1 1 3 8 7 4 5 6 10 2 11 9 A B Key A Electronic module B Base module 1 LED for module diagnostics 2 Labelling strip with Name of electronic module Order number Serial number Hardware version number 2D...

Страница 9: ...tighten the screw terminal on base modules with screw termin als With mechanism to operate the cage clamp on base modules with cage clamp ter minals 10 Round connection holes connection levels 1 2 3...

Страница 10: ...lowing is deemed improper use in particular Any component technical or electrical modification to the module Use of the module outside the areas described in this manual Any use of the module that is...

Страница 11: ...h and safety accident preven tion Have read and understood the information provided in this description under Safety And have a good knowledge of the generic and specialist standards applicable to the...

Страница 12: ...es 4 2 1 Functions The module routes the periphery supply from the module bus to the base module ter minals The module does not switch the periphery supply The periphery supply has no current limitati...

Страница 13: ...atic discharge Electrostatic discharge can damage components Ensure against discharge before touching the product e g by touching an earthed conductive sur face or by wearing an earthed armband 5 1 1...

Страница 14: ...ead module Please note For mechanical reasons it is not possible to mix base modules with screw terminals and base modules with cage clamp terminals All contacts should be protected from contamination...

Страница 15: ...es with outputs may only be inserted and removed when the load is switched off Unforeseeable error reactions may be triggered if modules are inserted and removed under load When an electronic module i...

Страница 16: ...tructions PSSu E PD T 21304 EN 04 16 5 3 1 Inserting an electronic module Procedure The electronic module must audibly lock into position 1 Mark the electronic module using the labelling strips 2 Sche...

Страница 17: ...ng operation The configuration data is re tained when a module is changed Effects System environment A In the event of a potential FS communication error the FS section of the PSSu sys tem and all rel...

Страница 18: ...ewdriver DIN 5264 A DIN 5264 A Strip the wire back 8 mm If necessary label the connection level with a colour marker 3 Base module with screw terminals Use a screwdriver to loosen the screw on the scr...

Страница 19: ...nalogue inputs outputs 1 5 mm2 AWG16 Communication cables 1 5 mm2 AWG16 Test pulse outputs 1 5 mm2 AWG16 Power supply 2 5 mm2 AWG12 Functional earth 2 5 mm2 AWG12 On base modules with screw terminals...

Страница 20: ...nked within the base mod ule 13 23 24 V periphery supply 13 23 linked within the base mod ule 14 24 24 V periphery supply 14 24 linked internally 21 11 22 12 23 13 24 14 Screw terminals PSSu BP C 1 8...

Страница 21: ...C T With C rail 11 21 0 V periphery supply 11 21 linked internally 12 22 0 V periphery supply 12 22 linked within the base mod ule 13 23 C rail supply 13 23 linked within the base mod ule 14 24 24 V p...

Страница 22: ...supply Ensure there is a sufficient supply Further information on PSSu error messages is available in the online help for the PSS WIN PRO system software 7 2 Display elements Legend LED on LED off 7 2...

Страница 23: ...0 V Module s current consumption with no load 10 mA 10 mA Module s power consumption with no load 0 24 W 0 24 W Environmental data 312195 314195 Climatic suitability EN 60068 2 1 EN 60068 2 14 EN 6006...

Страница 24: ...eration 10g 10g Duration 16 ms 16 ms Max operating height above sea level 2000 m 5000 m Airgap creepage In accordance with the standard EN 60664 1 EN 60664 1 Overvoltage category II II Pollution degre...

Страница 25: ...PSSu BP C 1 8 S T Base module with C rail and screw terminals T type 314 610 PSSu BP C 1 8 C Base module with C rail and cage clamp terminals 312 611 PSSu BP C 1 8 C T Base module with C rail and cag...

Страница 26: ...T p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document dependi...