Wiring
Operating Manual PSSu E F PS2(-T)(-R)
1002237-EN-05
22
}
On base modules with screw terminals:
– If you use a multi-strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
– Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
}
For use as a supply module to refresh the module supply and periphery supply
}
For use as a supply module to form supply groups
– To interrupt the incoming periphery supply and C-rail
– To provide subsequent modules with the module supply, periphery supply and C-
rail supply
Base module
Terminal configuration
Screw terminals:
PSSu BS-R 2/8 S
PSSu BS-R 2/8 S-T
Cage clamp terminals:
PSSu BS-R 2/8 C
PSSu BS-R 2/8 C-T
11: +24 V infeed for module
supply,
interrupted to the left
21: 0 V infeed for module
supply
12 -22: 0 V periphery supply,
interrupted to the left
(12-22 linked within the base
module)
13 -23: +24 V periphery sup-
ply, interrupted to the left
(13-23 linked within the base
module)
14-24 C-rail supply,
interrupted to the left
(14-24 linked within the base
module)
21
11
22
12
23
13
24
14