Commissioning
Operating Manual PSSnet GW1 MODEtherCAT
1002692EN03
31
}
Minimum conductor cross section on field connection terminals = 0.2 mm
2
(AWG24),
}
Maximum conductor cross section on field connection terminals = 2.5 mm
2
(AWG12),
}
Terminal points per connection: 2,
}
Stripping length: 9 mm.
6.2.2
Terminals
The plugin terminals for the inputs and outputs are not supplied with the system. You can
select between springloaded terminals and a screw connection.
6.3
Terminal configuration
Module supply
Terminal configuration
X4
4pin female con
nector
1
+24 V infeed for module supply
1
2
3
4
2
0 V infeed for module supply
3
Not connected
4
Functional earth
Terminal configuration
6.4
Interfaces
The following minimum requirements must be met:
}
Ethernet standards (min. Category 5) 100BaseTX
}
Doubleshielded twisted pair cable for industrial Ethernet use
}
Shielded RJ45 connectors (industrial connectors)
6.4.1
RJ45 interface
RJ45 socket, 8pin
PIN
Standard
Crossover
8 1
1
TD+ (T)
RD+ ()
2
TD (Transmit)
RD (Receive)
3
RD+ ()
TD+ (T)
4
n.c.
n.c.
5
n.c.
n.c.
6
RD (Receive)
TD (Transmit)
7
n.c.
n.c.
8
n.c.
n.c.
Interface assignment of RJ45 socket
n.c. = not connected