PSEN cs2.13p ATEX
Operating Manual PSEN cs2.13p ATEX
21133-EN-17
| 22
}
Please note the installation measures in accordance with EN ISO 14119 for a safety
switch design 4 and with level of coding High.
}
For simpler installation, the mounting brackets (see
Order reference for
Accessories [
29]
) can be used.
}
If using angled connector plugs, note the defined angle of the cable routing.
CAUTION!
Possible loss of the safety function by changing the release distance
S
ar
with non-flush installation
Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance
S
ar
can change.
– Check the assured release distance
S
ar.
Installation example:
The full face of the safety switch is installed on the subplate.
As a result, the edges of the safety switch base are protected from shock.
Procedure:
Fig.: Sensing faces on the sensor