Fieldbus Modules
Operating Manual Communication interfaces
1002971EN03
14
Double Word
Word
Byte
Content
7
14
28
Payload Byte 9
29
Payload Byte 10
15
30
Payload Byte 11
31
Payload Byte 12
4.1.2
Output data (from the PNOZmulti 2)
Double Word
Word
Byte
Content
0
0
0
State of virtual outputs on the PNOZmulti 2
fieldbus module.
The outputs are defined in the PNOZmulti
Configurator. Each output that is used is
given a number there, e.g. o0, o5...
The status of output o0 is stored in bit 0 of
byte 0; the status of output o5 is stored in
bit 5 of byte 0 etc.
1
1
2
3
1
2
4
5
3
6
7
2
4
8
9
5
10
11
3
6
12
13
7
14
15
4
8
16
LED status
17
Table number
9
18
Segment number
19
Payload Byte 0
5
10
20
Payload Byte 1
21
Payload Byte 2
11
22
Payload Byte 3
23
Payload Byte 4
6
12
24
Payload Byte 5
25
Payload Byte 6
13
26
Payload Byte 7
27
Payload Byte 8