Relay outputs
774789
774790
774791
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral
240 A²s
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
10 A
Blow-out fuse, slow
6 A
6 A
6 A
Blow-out fuse, gG
10 A
10 A
10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
6 A
6 A
6 A
Contact material
0,2µ Au
0,2µ Au
0,2µ Au
Conventional thermal
current while loading
several contacts
774789
774790
774791
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current
with 1 contact
8 A
8 A
8 A
Conv. therm. current
with 2 contacts
7,4 A
7,4 A
7,4 A
Conv. therm. current
with 3 contacts
6 A
6 A
6 A
Conv. therm. current
with 4 contacts
4 A
4 A
4 A
Times
774789
774790
774791
Switch-on delay
With automatic start
typ.
140 ms
140 ms
140 ms
With automatic start
max.
200 ms
200 ms
200 ms
With automatic start
after power on typ.
150 ms
150 ms
150 ms
With automatic start
after power on max.
220 ms
220 ms
220 ms
With manual start typ.
160 ms
160 ms
160 ms
With manual start max.
200 ms
200 ms
200 ms
Delay-on de-energisation
With E-STOP typ.
15 ms
15 ms
15 ms
With E-STOP max.
30 ms
30 ms
30 ms
With power failure typ.
50 ms
50 ms
50 ms
With power failure max.
100 ms
100 ms
100 ms
Recovery time at max.
switching frequency 1/s
After E-STOP
50 ms +tv
50 ms +tv
50 ms +tv
After power failure
150 ms
150 ms
150 ms
Delay time tv
0,1 s, 0,2 s, 0,3 s, 0,4 s,
0,5 s, 0,6 s, 0,7 s, 0,8 s, 1
s, 1,5 s, 2 s, 3 s
0,05 s, 0,5 s, 1 s, 2 s, 4 s,
6 s, 8 s, 10 s, 15 s, 20 s,
25 s, 30 s
0,15 s, 5 s, 10 s, 20 s, 40
s, 60 s, 80 s, 100 s, 150
s, 200 s, 250 s, 300 s
Time accuracy
-15 %/+15 % +50 ms
-15 %/+15 % +50 ms
-15 %/+15 % +50 ms