![Pilz PNOZ V Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/pilz/pnoz-v/pnoz-v_operating-manual_1556829016.webp)
PNOZ V
Operating Manual PNOZ V
21115-EN-07
| 15
Relay outputs
774789
774790
774791
Utilisation category
In accordance with the
standard
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
Utilisation category of
safety contacts
AC1 at
400 V
400 V
400 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
5 A
5 A
5 A
Max. power
2000 VA
2000 VA
2000 VA
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category of
safety contacts delayed
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
4 A
4 A
4 A
Max. power
1000 VA
1000 VA
1000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
4 A
4 A
4 A
Max. power
100 W
100 W
100 W
Utilisation category of
auxiliary contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
2000 VA
2000 VA
2000 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
8 A
8 A
8 A
Max. power
200 W
200 W
200 W
Utilisation category
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category of
safety contacts
AC15 at
230 V
230 V
230 V
Max. current
5 A
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
7 A
7 A
7 A