Commissioning
Operating Manual PNOZ m ES Powerlink
1003193-EN-05
15
6.2
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
}
24 V
terminal: + 24 VDC
}
0 V
terminal: 0 V
}
Protect the supply voltage as follows:
–
Circuit breaker, characteristic C - 6 A
or
–
Blow-out fuse, slow, 6A
6.3
Interface assignment
RJ45 socket
8-pin
PIN
Standard
8 1
1
TD+ (T)
2
TD- (Transmit-)
3
RD+ ()
4
n.c.
5
n.c.
6
RD- (Receive-)
7
n.c.
8
n.c.
n.c.: Not connected
6.4
Download modified project to the PNOZmulti system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.
NOTICE
For the commissioning and after every program change, you must check
whether the safety devices are functioning correctly.