Wiring

Please note:

}

Information given in the "

Technical details [

 14]

" must be followed.

}

Outputs 13-14, 23-24, 33-34 are safety contacts, outputs 41-42, 53-54 are auxiliary
contacts (e.g. for display).

}

Do 

not

 use auxiliary contacts 41-42, 53-54 and semiconductor output Y35 for safety cir-

cuits!

}

Do not connect undesignated terminals.

}

To prevent contact welding, a fuse should be connected before the output contacts (see

Technical details [

 14]

).

}

Calculation of the max. cable length l

max 

in the input circuit:

R

lmax

R

/ km

I

max

 =

R

lmax

 = max. overall cable resistance (see 

Technical details [

 14]

)

R

l

 / km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Do not switch low currents using contacts that have been used previously with high cur-
rents.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.

}

The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.

}

Ensure the wiring and EMC requirements of EN 60204-1 are met.

}

Terminals S11 and S33, and terminals Y1 and S34 are linked internally and either can
be used.

Important for detection of shorts across contacts:

As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during
the final control check. If there is a danger of exceeding the cable runs, we recommend the
following test after the installation of the device:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S12, S22 for detecting shorts across the inputs.
3. The unit's fuse must be triggered and the output contacts must open. Cable lengths in

the scale of the maximum length can delay the fuse triggering for up to 2 minutes.

4. Reset the fuse: remove the short circuit and switch off the supply voltage for approx. 1

minute.

Содержание PNOZ 15

Страница 1: ...PNOZ 15 Operating Manual 18492 EN 04 Safety relays...

Страница 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Страница 3: ...liability 6 Disposal 6 For your safety 6 Unit features 7 Safety features 7 Block diagram terminal configuration 7 Function Description 8 Operating modes 8 Timing diagram 9 Installation 9 Wiring 10 Pr...

Страница 4: ...y important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures t...

Страница 5: ...nt electrical installation The product is designed for use in an industrial environment The product may cause interference if installed in other environments If installed in other environments measure...

Страница 6: ...e generic and specialist standards applicable to the spe cific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the...

Страница 7: ...fety relay meets the following safety requirements The circuit is redundant with built in self monitoring The safety function remains effective in the case of a component failure The correct opening a...

Страница 8: ...nternal fuse thermal circuit breaker has not blown If there is a fault on the safety relay a high signal is present at Y35 the FAULT LED lights Once the cause of the fault has been removed the fuse mu...

Страница 9: ...normally open Out semi FAULT Semiconductor output fault 1 Automatic start 2 Manual start a Input circuit closes before start circuit b Start circuit closes before input circuit t1 Switch on delay t2...

Страница 10: ...s with capacitive and in ductive loads The power supply must comply with the regulations for extra low voltages with protect ive electrical separation SELV PELV in accordance with VDE 0100 Part 410 En...

Страница 11: ...S12 S1 S11 S12 S52 S22 S21 E STOP with detection of shorts across contacts S1 S22 S21 S12 S11 S52 S11 Safety gate without detection of shorts across contacts S1 S22 S21 S11 S52 S12 S1 S2 S22 S21 S11...

Страница 12: ...t up test S2 S1 S33 S34 Manual start S33 S34 S3 NOTICE In the event of an automatic start or manual start with bridged start contact fault The unit starts up automatically when the safeguard is reset...

Страница 13: ...t the safety contacts on the relay outputs open correctly Open the safety contacts switch off output and start the device again so that the internal diagnostics can check that the safety contacts open...

Страница 14: ...ons If the contacts have welded reactivation will not be possible after the input circuit has opened LED POWER does not light Short circuit or no supply voltage Dimensions in mm 121 4 76 75 2 95 87 3...

Страница 15: ...nnel with detection of shorts across con tacts at UB DC 5 Ohm Semiconductor outputs Number 1 Voltage 24 V Current 50 mA External supply voltage 24 V Voltage tolerance 30 30 Short circuit proof yes Rel...

Страница 16: ...ent 2 A External contact fuse protection safety contacts In accordance with the standard EN 60947 5 1 Max melting integral 240 A s Blow out fuse quick 10 A Blow out fuse slow 6 A Blow out fuse gG 10 A...

Страница 17: ...Frequency 10 55 Hz Amplitude 0 35 mm Airgap creepage In accordance with the standard EN 60947 1 Overvoltage category III II Pollution degree 2 Rated insulation voltage 400 V Rated impulse withstand vo...

Страница 18: ...function must be considered when calculating the safety characteristic data INFORMATION A safety function s SIL PL values are not identical to the SIL PL values of the units that are used and may be d...

Страница 19: ...sed in the calculation To increase the service life sufficient spark suppression must be provided on all output contacts With capacitive loads any power surges that occur must be noted With DC con tac...

Страница 20: ...fetyNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document d...

Отзывы: