Wiring

Operating Manual PMI 6
1003280-EN-01

18

6

Wiring

6.1

General wiring guidelines

}

Electrical or electronic components that could cause interference (contactors, thyristors,
relay coils and solenoid valve coils) should be physically separate from data cables.
We recommend you use a sheet metal (MU metal) bulkhead between both areas.

}

Data cables and power cables should be laid separately to avoid capacitive and induct-
ive transmission (recommended minimum distance = 10 cm/3.94").

}

Shielded data cables should also be laid in a different cable duct to the main power
cables.

}

Power cables should be as short as possible.

}

Power cables should be twisted pair cables.

}

We recommend a max. length of 2 m for the USB cable, to guarantee reliable data
transfer.

}

Use cables with a cross section of 0.5 … 1.0 mm², ferrules without plastic collar in ac-
cordance with DIN 46228/1 for the fieldbus terminal connections.

6.1.1

Shielding

}

Connect the power cable shield with low impedance to earth.

}

Use only shielded data lines.

}

For high-frequency reasons, we recommend that the shielding on the data line cable
(RS 232 cable) is earthed on both sides. If you are using longer cables and there is the
possibility of transient currents, we recommend one of the following methods:
– Use equipotential bonding conductors
– Use electrical isolation

}

Connect data line shields to a bus bar.

}

Make the connection of the bus bar to the control cabinet/system as short and with as
low impedance as possible.

}

Fasten the braided shield to the shield bar over as large a surface area as possible
(e.g. with metal hose clips or PUK cable clips).

6.1.2

Measures to protect against interference voltages

}

Wire-up inductive loads (e.g. contactor coils, relay coils and solenoid valve coils) using
suppression elements (e.g. RC networks). This is particularly important if these induct-
ive loads are very close to the power supply or are fed from the same supply.

}

If strong magnetic fields are present, we recommend you use a bulkhead separator, i.e.
metal sheet (MU-metal).

Содержание PMI 6

Страница 1: ...PMI 6 Operating Manual 1003280 EN 01 Operator terminals...

Страница 2: ...umentation will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Interne...

Страница 3: ...fety regulations 10 3 3 1 Installation site 10 3 3 2 Measures to protect against interference 11 3 3 3 Supply voltage 11 3 3 4 Operation 11 3 3 5 Maintenance 12 Section 4 Function description 13 4 1 F...

Страница 4: ...Start 25 7 2 11 Taskbar and desktop 26 7 2 12 Network servers 26 7 2 13 Internet options 26 7 3 Start mode 26 7 3 1 Automatically copy to system folder windows 26 7 3 2 Batch file PMIStart cmd 26 7 3...

Страница 5: ...ead and understood this document The document should be retained for future ref erence 1 3 Definition of symbols Information that is particularly important is identified as follows DANGER This warning...

Страница 6: ...n which the product or devices could be dam aged and also provides information on preventive measures that can be taken It also highlights areas within the text that are of particular import ance INFO...

Страница 7: ...erate and monitor technical processes 2 1 1 Unit features Capacitive touchscreen Character set Unicode 1 SD card slot Memory 512 MB DDR SDRAM 1 serial interface 1 Ethernet interface 1 CANopen interfac...

Страница 8: ...N 01 8 2 2 Front view 1 Legend 1 Touchscreen see Technical details 40 2 3 Scope of supply Operator terminal Retaining clamps Connector plug for power supply Projection stand RJ45 cable for fieldbus ju...

Страница 9: ...AUTION The unit is not designed for use in applications with stringent safety require ments e g E STOP The following is deemed improper use in particular Any component technical or electrical modifica...

Страница 10: ...ation 3 2 2 Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to no...

Страница 11: ...central earth point in star form A cable cross sec tion of at least 1 5 mm should be used for the connection Connections should be kept as short as possible 3 3 3 Supply voltage The supply voltage mu...

Страница 12: ...1003280 EN 01 12 3 3 5 Maintenance Do not use thinners or organic solvents to clean the unit and touchscreen surface Further information on care and maintenance of the touchscreen can be found in the...

Страница 13: ...own on the display and directly influenced via the touchscreen A fieldbus interface CANopen Ethernet e g Modbus and an RS232 interface are available for the transfer of data e g diagnostic data and fo...

Страница 14: ...Function description Operating Manual PMI 6 1003280 EN 01 14 7 Fieldbus junction box 8 Supply voltage 24 VDC 9 Serial interface COM1 RS232 10 USB Slave 11 USB Host 1 12 USB Host 2 13 Functional earth...

Страница 15: ...operator 5 1 1 Installation site and unit surroundings NOTICE Damage due to heat accumulation To avoid the accumulation of heat a distance of 10 cm 3 94 should be maintained around the device To achi...

Страница 16: ...mm 216 8 504 153 6 024 332 13 071 222 8 740 b2 mm h2 mm t2 mm 199 7 835 136 5 354 33 5 1 319 315 12 402 205 8 071 31 5 1 240 b3 mm h3 mm t3 mm 146 6 5 772 101 3 976 45 5 1 791 146 6 5 772 101 3 976 4...

Страница 17: ...on of heat a distance of 10 cm 3 94 should be maintained around the device Ensure the information given for the ambient and operating temperatures in the tech nical details is observed IP65 protection...

Страница 18: ...Shielding Connect the power cable shield with low impedance to earth Use only shielded data lines For high frequency reasons we recommend that the shielding on the data line cable RS 232 cable is eart...

Страница 19: ...24 V DC supply is located on the side of the housing 1 2 3 Fig Layout of supply voltage connector 1 Functional earth 2 0 V 3 24 V DC 6 3 Connection example 1 2 3 4 5 3 4 5 6 Fig Connection example Le...

Страница 20: ...earthing bolts housing 6 Data line shield 0 V and are connected internally 6 4 Interfaces Connect X7 and X7 fieldbus to the fieldbus junction cable 6 4 1 RS232 interface COM1 GND DTR TxD RxD DCD RI C...

Страница 21: ...card supplied on which the PMI Assistant is installed must be connected to do this When the SD card is not connected the Control Panel is started Further information on the PMI Assistant can be found...

Страница 22: ...a password Defining a password Enter a password Enter the password again under Confirm pass word Change password Same as for defining a password Delete password Deselect Ask for master password If you...

Страница 23: ...assword protected area This area is protected with a password Remove Remove Control Panel applets from the password protected area This area is not protec ted with a password INFORMATION Add Password...

Страница 24: ...ON The ex works setting for the network user is User name pmiuser Password 1234 7 2 3 Date time Setting the date time time zone and winter summer time 7 2 4 Display Setting the background image and ba...

Страница 25: ...al settings Regional settings number format currency time date 7 2 8 Storage Manager Format partition memory 7 2 9 System Display modify system properties relationship between program memory file mana...

Страница 26: ...led on the external Storage Card using fontreg see Windows CE Shell commands Pilz expansions 35 7 3 2 Batch file PMIStart cmd PMIStart cmd is a CE Shell command batch file which is executed sequential...

Страница 27: ...static IP address see Network and dial up 24 7 3 5 Various basic settings Regional settings English currency date time numbers User input language English fixed Input language English keyboard see Reg...

Страница 28: ...regular intervals Use a damp cloth to do this NOTICE Make sure the unit is switched off before cleaning it This prevents you from accidentally triggering functions when you touch the touchscreen Clea...

Страница 29: ...xception Handling and Runtime Type Information Full C Runtime Standard IO STDIO Standard IOASCII STDIO Standard String Functions ASCII corestra Component Services COM Lightweight Directory Access Prot...

Страница 30: ...Server Simple Network Time Protocol SNTP SNTP Client with DST SNTP Server Telnet Server Web Server HTTPD Active Server Pages ASP Support Web Server Administration ISAPI WEBDAV Support Core OS Service...

Страница 31: ...CD UDFS File System exFAT File System FAT File System Partition Driver Release Directory File System Storage Manager Control Panel Applet Transaction Safe FAT File System TFAT System Password Fonts T...

Страница 32: ...Locale Specific Support English US US Keyboard Internet Client Services Browser Application Internet Explorer 7 for Windows Embedded CE Standard Components Internet Explorer 7 Sample Browser Internet...

Страница 33: ...gine Minimal GDI Configuration Minimal GWES Configuration Minimal Input Configuration Minimal Window Manager Configuration Touch Gesture GWES component Shell AYGShell API Set Command Shell Command Pro...

Страница 34: ...Separates a command or several commands and sends the output of a command as input for the command that follows file1 Name of the file that includes the output file2 Name of the file that includes th...

Страница 35: ...s comments to a batch file RENAME REN Changes the name of one or several files RMDIR RD Deletes a directory SET Sets or removes an environment variable or shows the values of all environment variables...

Страница 36: ...tion after formatting with a low formatting rate A Overwrites the standard sizes of memory allocation T Creates a TFAT format Y Confirmation kill Command used to force the completion of a process Synt...

Страница 37: ...fo Parameter Description InFile File name temp Temporarily saved the present registration is not overwritten info Status information on the success failure of the ac tion regsave Command used to perma...

Страница 38: ...liseconds usrmgr Command used to manage network subscribers Syntax usrmgr a d l user name password gn gd gl gm gat grf Parameter Description a user name password Add or update network subscriber d use...

Страница 39: ...Outputs the serial number r Outputs the order number c Outputs the chip set version xcopy Command used to copy files and directory structures Syntax xcopy c h y title sourcedir targetdir Parameter De...

Страница 40: ...sh 512 MB 512 MB Real time clock yes yes Removable data medium 265607 265612 Type SD card SD card USB interface 265607 265612 Number of USB Hosts 2 2 CANopen interface 265607 265612 Connection type 9...

Страница 41: ...MC EN 61000 6 2 EN 61000 6 4 EN 61000 6 2 EN 61000 6 4 Vibration In accordance with the standard EN 60068 2 6 EN 60068 2 6 Frequency 10 150 Hz 10 150 Hz Acceleration max 1g max 1g Shock stress In acco...

Страница 42: ...42 11 Order reference 11 1 Product Product type Features Order No PMI 607 Control Operator terminal 800 x 480 pixel resolution ca pacitive touchscreen 265 607 PMI 612 Control Operator terminal 1280 x...

Страница 43: ...p ThE SPIrIT Of SAfETY are registered and protected trademarks of Pilz Gmbh Co KG in some countries We would point out that product features may vary from the details stated in this document dependin...

Отзывы: