Relay outputs
787949
787950
787951
External contact fuse pro-
tection, safety contacts
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Max. melting integral
66 A²s
66 A²s
66 A²s
Blow-out fuse, quick
6 A
6 A
6 A
Blow-out fuse, slow
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24V
AC/DC, characteristic
B/C
4 A
4 A
4 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral
66 A²s
66 A²s
66 A²s
Blow-out fuse, quick
6 A
6 A
6 A
Blow-out fuse, slow
4 A
4 A
4 A
Blow-out fuse, gG
6 A
6 A
6 A
Circuit breaker 24 V
AC/DC, characteristic
B/C
4 A
4 A
4 A
Conventional thermal cur-
rent
6 A
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
0,2 µm Au
Conventional thermal
current while loading
several contacts
787949
787950
787951
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current
with 1 contact
6 A
6 A
6 A
Conv. therm. current
with 2 contacts
4 A
4 A
4 A
Times
787949
787950
787951
Max. switch-on delay
After motor standstill
max.
1.500 ms
1.500 ms
1.500 ms
After power on max.
2.200 ms
2.200 ms
2.200 ms
Delay-on de-energisation
After motor on max.
170 ms
170 ms
170 ms
Recovery time at max.
switching frequency 1/s
After motor on
2.200 ms
2.200 ms
2.200 ms
Supply interruption before
de-energisation
20 ms
20 ms
20 ms
Simultaneity, channel 1
and 2 max.
7 s
7 s
7 s
Environmental data
787949
787950
787951
Climatic suitability
EN 60068-2-78
EN 60068-2-78
EN 60068-2-78