PSWZ X1P
Operating Manual PSWZ X1P
21005-EN-11
| 20
Relay outputs
777949
777950
Utilisation category of auxiliary con-
tacts
AC15 at
230 V
230 V
Max. current
3 A
3 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
4 A
4 A
Utilisation category in accordance
with UL
Voltage
240 V AC G. P.
240 V AC G. P.
With current
6 A
6 A
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
66 A²s
66 A²s
Blow-out fuse, quick
6 A
6 A
Blow-out fuse, slow
4 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24V AC/DC,
characteristic B/C
4 A
4 A
External contact fuse protection,
auxiliary contacts
Max. melting integral
66 A²s
66 A²s
Blow-out fuse, quick
6 A
6 A
Blow-out fuse, slow
4 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24 V AC/DC,
characteristic B/C
4 A
4 A
Conventional thermal current
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
Conventional thermal current
while loading several contacts
777949
777950
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
6 A
6 A
Conv. therm. current with 2 con-
tacts
4 A
4 A
Times
777949
777950
Max. switch-on delay
After motor standstill max.
1.500 ms
1.500 ms
After power on max.
2.200 ms
2.200 ms
Delay-on de-energisation
After motor on max.
170 ms
170 ms
Recovery time at max. switching
frequency 1/s
After motor on
2.200 ms
2.200 ms