PSWZ X1P
Operating Manual PSWZ X1P
21005-EN-11
| 17
Fault indicators
FAULT
Diagnostics: Simultaneity requirement is exceeded or single-channel exceeding
and subsequent value falls again below the standstill threshold U
Off
}
Remedy: Reset the error by supplying a High signal and then a Low signal at
the Reset input.
Faults – Interference
}
LED "POWER" does not light: Short circuit or no supply voltage.
}
Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
}
When exceeding the simultaneity time the safety contacts 13-14, 23-24 remain open.
Dimensions in mm
* with spring-loaded terminals