PZW
Operating Manual PZW
19157-EN-07
18
Relay outputs
774042
774044
774048
Utilisation category of
safety contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
6 A
6 A
6 A
Max. power
1500 VA
1500 VA
1500 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
6 A
6 A
6 A
Max. power
150 W
150 W
150 W
Utilisation category of
auxiliary contacts
AC1 at
240 V
240 V
240 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
6 A
6 A
6 A
Max. power
1500 VA
1500 VA
1500 VA
DC1 at
24 V
24 V
24 V
Min. current
0,01 A
0,01 A
0,01 A
Max. current
6 A
6 A
6 A
Max. power
150 W
150 W
150 W
Utilisation category
In accordance with the
standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Utilisation category of
safety contacts
AC15 at
230 V
230 V
230 V
Max. current
4 A
4 A
4 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
3 A
3 A
3 A
Utilisation category of
auxiliary contacts
AC15 at
230 V
230 V
230 V
Max. current
4 A
4 A
4 A
DC13 (6 cycles/min) at
24 V
24 V
24 V
Max. current
3 A
3 A
3 A
Utilisation category in ac-
cordance with UL
Voltage
240 V AC G. P.
240 V AC G. P.
240 V AC G. P.
With current
6 A
6 A
6 A
Voltage
24 V DC Resistive
24 V DC Resistive
24 V DC Resistive
With current
5 A
5 A
5 A
Pilot Duty
B300, R300
B300, R300
B300, R300