PSEN sl1.0n 1.1/2.1/2.2
Operating Manual PSEN sl1.0n 1.1/2.1/2.2
22174EN03
9
Function description
U
B
A1
A2
S31
12
22
Power supply
Power/Fault
&
&
Safety Gate
Lock
Receiver
Magnet
Actuator
There is a high signal at safety outputs 12 and 22 if the following occur
simultaneously
:
}
The actuator is within the response range (safety gate closed) and
}
Input S31 is high (control command for magnetic guard locking) and
}
The holding force of the locking magnet has been tested successfully.
Safety outputs 12 and 22 are low if
at least
one
of the following conditions are met:
}
The actuator is outside the response range or
}
Input S31 (control command for magnetic guard locking) is low or
}
The holding force of the locking magnet has not been tested successfully.
Magnetic guard locking device and magnet monitoring
}
The locking magnet is switched on if S31 (control command for magnetic guard locking)
is high and the actuator is detected (safety gate closed).
}
The holding force of the locking magnet is tested on powerup.
}
After S31 switches to low, wait at least 500 ms until S31 is switched back to high. Also
note the max. switching frequency (see
Technical details [
22]
).
If an open winding or a winding short circuit is detected on a locking magnet that is
switched on, safety outputs 12 and 22 switch to a low state.
}
For physical reasons, a remanence (residual magnetism) remains after the locking
magnet is switched off; this is dissipated the first time the sensor and actuator are sep
arated.
}
If the safety gate is in a locked condition and is opened by force, the safety outputs will
shut down.