Function description
Operating Manual PSSu E F 4DI(-T)(-R),
21310-EN-08
14
Further information on configuration is available in the PSSuniversal Configurator's online
help.
4.5.1.1
Addresses in the process image
The module occupies 4 consecutive bit addresses in the process image. The process im-
age in which the inputs are shown depends on the configuration.
Configuration
SafetyBUS p
Standard bus system
FS-PII
ST-PII
ST-PIO
None
4 Bit
(e. g.: 32.00 … 32.03)
- - -
- - -
Read ST (“R”)
4 Bit
- - -
4.5.2
PSSu assignment in system environment B
Data access is via pre-defined I/O data types:
I/O data name
I/O data type
I/O data element
Meaning
I0(11), I1(21), I2(14), I3(24)
FS_I_DI
Data: SAFEBOOL
Input data I0 ... I3