Hearth 

The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is 
not independently supported. The weight of the stove is indicated in the brochure. 
 
The stove should always be installed on a non-combustible hearth of a size and construction that is 
in accordance with the provisions of the current Building Regulations Approved Document J. 
 
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls 
adjacent to the hearth should comply with the guidance on the separation of combustible material 
given in Building Regulations Approved Document J and also in these stove instructions. 
 

If the stove is to be installed on a combustible floor surface, it must be covered with 
a non-combustible material at least 12mm thick, in accordance with Building       
Regulations Approved Document J, to a distance of 30 cm in front of the stove and 
15 cm to each side  measuring from the door of the combustion chamber 
 
Combustion air supply 

In order for the stove to perform efficiently and safely there should be an adequate air supply into the 
room in which the stove is installed to provide combustion air.  This is particularly necessary if the 
room is double-glazed or a flue draught stabiliser is operating in the same room as the appliance. It 
may be necessary to increase the air vent size in property with low air permeability ( < 5.0 m

3

 /(h.m

2

). 

The provision of air supply to the stove must be in accordance with current Building Regulations   
Approved   Document J. An opening window is not appropriate for this purpose. 
IMPORTANT NOTE: If applicable and the appliance is being fitted within an existing fireplace recess, 
specialist advice should be sought before fitting any permanent ventilation within this area. 
 

Connection to chimney 

Stoves may have a choice of either a rear or top flue gas connector that allows connection to either a 
masonry chimney or a prefabricated factory made insulated metal chimney in accordance with their 
instructions. In some cases it may be necessary to fit an adaptor to increase the diameter of the flue 
to the minimum required 150 mm section of the chimney or liner. 
 

Electrical Services 

The installation of any electrical services during the installation of this appliance must be carried out 
by a registered competent electrician and in accordance with the requirements of the latest issue of 
BS 7671 
 

Carbon Monoxide Alarm 

A carbon monoxide alarm complying with BS EN 50292 must be fitted in the same room as the     
appliance. It should be positioned on the ceiling at least 300mm from any wall or, if it is located on a 
wall, as high up as    possible (above any doors and windows) but not within 150mm of the ceiling. 
The alarm should also be between 1m and 3m horizontally from the appliance. 
 

Commissioning and handover 

Ensure loose parts are fitted in accordance with the instructions given in the instruction booklet. 
 
On completion of the installation allow a suitable period of time for any fire cement and mortar to dry 
out, when a small fire may be lit and checked to ensure the smoke and fumes are taken from the 
stove up the chimney and emitted safely to atmosphere. Do not run at full output for at least 24 
hours. 
 
On completion of the installation and commissioning ensure that the operating instructions for the 
stove are left with the customer. Ensure to advise the customer on the correct use of the appliance 
with the fuels likely to be used on the stove and warn them to use only the recommended fuels for 
the stove. 
 
Advise the user what to do should smoke or fumes be emitted from the stove. The customer should 
be warned to use a fireguard to BS 8423:2002 in the presence of children, aged and/or infirm per-
sons. 

 

 

Содержание E903

Страница 1: ...d Belper Derbyshire DE56 1UU Tel 01773 820940 Fax 01773 820477 E mail info robeys co uk Web Site www robeys co uk Riverside Goods Road Belper Derbyshire DE56 1UU Tel 01773 820940 Fax 01773 820477 E ma...

Страница 2: ...E903 2 July 2012...

Страница 3: ...tective equipment Metal Parts When installing or servicing this stove care should be taken to avoid the possibility of personal injury STOVE PERFORMANCE In the UK the stove has been approved by HETAS...

Страница 4: ...ove is fitted in place of an open fire then the chimney should be swept one month after installation to clear any soot falls which may have occurred due to the difference in combustion between the sto...

Страница 5: ...tion within this area Connection to chimney Stoves may have a choice of either a rear or top flue gas connector that allows connection to either a masonry chimney or a prefabricated factory made insul...

Страница 6: ...xpectedly follow the instructions given under Warning Note above Use of fireguard When using the stove in situations where children aged and or infirm persons are present a fireguard must be used to p...

Страница 7: ...as directed in the instructions Dampers left open Operation with the air controls or dampers open can cause excess smoke The appliance must not be operated with air controls or dampers left open exce...

Страница 8: ...fire bars or damage to the glass may be caused when the doors are closed Flueway cleaning It is important that the baffle plate and all the stove flueways are kept clean When burning smokeless fuels t...

Страница 9: ...E903 9 July 2012...

Страница 10: ...duct identification data 21 2 6 Dimensions e903K 22 2 7 Dimensions e903M 22 2 8 Dimensions e903S 22 3 0 USE 23 3 1 Fuel 23 3 2 Combustion air regulation 24 3 3 Lighting for the first time 24 3 4 Light...

Страница 11: ...E903 11 July 2012 N O T F O R U K U S E...

Страница 12: ...E903 12 July 2012...

Страница 13: ...E903 13 July 2012...

Страница 14: ...E903 14 July 2012 Fig 10 11 The illustration and table identify the minimum requirements as dictated by Building Regulations...

Страница 15: ...E903 15 July 2012...

Страница 16: ...E903 16 July 2012...

Страница 17: ...E903 17 July 2012 Minimum 45cm Minimum 45cm N O T F O R U K U S E N O T F O R U K U S E N O T F O R U K U S E...

Страница 18: ...E903 18 July 2012...

Страница 19: ...E903 19 July 2012 N O T F O R U K U S E...

Страница 20: ...E903 20 July 2012...

Страница 21: ...E903 21 July 2012...

Страница 22: ...E903 22 July 2012...

Страница 23: ...E903 23 July 2012...

Страница 24: ...E903 24 July 2012...

Страница 25: ...E903 25 July 2012...

Страница 26: ...E903 26 July 2012...

Страница 27: ...E903 27 July 2012...

Страница 28: ...E903 28 July 2012...

Страница 29: ...E903 29 July 2012...

Страница 30: ...E903 30 July 2012...

Страница 31: ...E903 31 July 2012...

Страница 32: ...E903 32 July 2012...

Страница 33: ...E903 33 July 2012 Riverside Goods Road Belper Derbyshire DE56 1UU Tel 01773 820940 Fax 01773 820477 E mail info robeys co uk Web Site www robeys co uk...

Отзывы: