5.5 Temperature Scale
Temperature zones may be set in either Fahrenheit or Celsius
degrees. The default temperature scale is Fahrenheit. To change to
Celsius:
1. Press SENSOR ON/OFF.
SENSOR
ON/OFF
2. Press °F / °C. The Model 800 responds:
“Degrees Celsius”
indicating Celsius scale has replaced Fahrenheit scale.
TEST
°F/°C
#
3. To return to Fahrenheit scale, repeat the key sequence. The
Model 800 responds:
“Degrees Fahrenheit”
indicating Fahrenheit
scale is in effect.
NOTE
When switching from Fahrenheit to Celsius, or vice
versa, the change applies to all zones configured to
read temperature. When switching temperature scales
it is important to reset high and low temperature lim-
its on all temperature zones. Refer to Section 5.4.1 to
reset temperature limits.
5.6 Temperature Calibration
To compensate for minor variances in sensor accuracy, an offset
may be programmed for each temperature zone. The amount
of offset is measured in degrees Fahrenheit or degrees Celsius.
Adjustments are possible within a range from -10 degrees to +10
degrees. For example, if zone 3 is sensing temperature and is
reading 1 degree too high, then the calibration for zone 3 is set at
-1 to obtain an accurate reading.
5.6.1 Programming Temperature Calibration
1. Press SET.
SET
2. Press CALIBRATE.
6
CALIBRATE
Chapter 5: Alarm Programming
76
Содержание Sensaphone 800
Страница 2: ......
Страница 3: ...SENSAPHONE Model 800 User s Manual Version 1 1 PHONETICS INC ...
Страница 14: ...Sensaphone Model 800 User s Manual xii ...
Страница 20: ...xviii ...
Страница 42: ...Sensaphone Model 800 User s Manual 39 ...
Страница 70: ...Sensaphone Model 800 User s Manual 67 ...
Страница 130: ...127 ...
Страница 132: ...129 ...
Страница 136: ...133 ...