Ancillary Product Specifications
Phoenix Recommended Cables
35
MKT-0262 MPC-1748 Rev 02/13
APM2 Rough-In Installation Guide
1
Load is 96 VA when power is provided
b
y a 100 VA transformer with external 4 amp slow
b
low fuse.
2
Load is 100 VA when power is provided
b
y a 100 VA transformer with internal circuit
b
reaker.
4.5.1 MS/TP Specifications for Alternate Cable Solutions
1. An MS/TP (EIA-485) network shall use shielded, twisted-pair cable with characteristic impedance
between 100 and 130
Ω
..
2. Distributed capacitance between conductors shall be less that 100 pF per meter (30 pf per foot).
3. Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per
foot).
4. Foil or braided shields are acceptable. The maximum recommended length of an MS/TP segment is 1200
meters (4000 feet) with AWG 18 (0.82 mm
2
conductor area) cable.
5. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of
EIA-485 for MS/TP cable requirements.
4C
MS/TP
Yes
Shielded
24
Belden 82729
(100 ohm)
See
specifications
below for
alternate cable
solutions
1: White with Blue
stripe
2: Blue with White
stripe
3: White with Orange
stripe
4: Orange with White
stripe
Shield with
drain
4C
MS/TP
Yes
Shielded
24
Belden 88102
(100 ohm)
See
specifications
below for
alternate cable
solutions
1: White with Blue
stripe
2: Blue with White
stripe
3: White with Orange
stripe
4: Orange with White
stripe
Shield with
drain
Cable
Type
Plenum
Rated
Function
Wire
Gauge
Primary
Vendor/Part #
Alternate
Vendor/Part #
Color Code
Notes