Interfaces of the Device
8095_en_00
PHOENIX CONTACT
4-17
The maximum cable length depends on the baud rate (DIN EN 19245 Part 3).
4.3.3.3
Termination
Terminate the PROFIBUS at both ends by terminating resistors. If you are using special
PROFIBUS connectors, these resistors are usually integrated into the connector and can be
connected.
4.3.3.4
Diagnostics
A diagnostics LED is located on the rear of the operating device. The LED shows the states
of the bus system.
The diagnostics LED on the operating device has the following functions:
Table 4-17
Baud rate PROFIBUS-DP
Baud Rate
Cable Length
187.5 kBit/s
1000 m
500 kBit/s
400 m
1500 kBit/s
200 m
3000 to 12000 kBit/s
100 m
Table 4-18
Function of the PROFIBUS-DP diagnostics LED
Color
State
Function
Green
On
Communication Active
Содержание UM EN TP 3 Series
Страница 1: ...AUTOMATION User Manual UM EN TP 3xxx Touch Panel with TFT Display...
Страница 2: ......
Страница 6: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T PHOENIX CONTACT 8095_en_00...
Страница 14: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 4 PHOENIX CONTACT 8095_en_00 Figure 2 3 TP 3070T...
Страница 15: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 5 Figure 2 4 TP 3105T...
Страница 16: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 6 PHOENIX CONTACT 8095_en_00 Figure 2 5 TP 3121T...
Страница 36: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 3 2 PHOENIX CONTACT 8095_en_00...
Страница 56: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 4 20 PHOENIX CONTACT 8095_en_00...
Страница 60: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 5 4 PHOENIX CONTACT 8095_en_00...
Страница 68: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 6 8 PHOENIX CONTACT 8095_en_00...