TRIO-PS-2G/3AC/24DC/40
105907_en_00
PHOENIX CONTACT
8 / 25
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
The ambient temperature (operation) refers to UL 508 surrounding air temperature.
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤
95 % (at 25 °C, non-condensing)
Installation height
≤
4000 m (> 2000 m, Derating: 10 %/1000 m)
Vibration (operation)
DNV
GL CG-0339 / Class B
2 Hz - 100 Hz resonance search, 90 min. in resonance,
2 Hz - 25 Hz, ±1.6 mm amplitude,
25 Hz - 100 Hz, 4g acceleration
Shock
18 ms, 30g, in each space direction (according to IEC 60068-
2-27)
Degree of pollution
2
Climatic class
3K3 (in acc. with EN 60721)
Overvoltage category
EN 60950-1
EN 62477-1
II
III
Standards
Safety of power supply units up to 1100
V (insulation
distances)
DIN EN 61558-2-16
Electrical safety (of information technology equipment)
IEC 60950-1/VDE 0805 (SELV)
SELV
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Safe isolation
DIN VDE 0100-410
Limitation of mains harmonic currents
EN 61000-3-2
Rail applications
EN 50121-4
Approvals
UL
UL Listed UL 508
UL/C-UL Recognized UL 60950-1
Current approvals/permissions for the product can be found in the download area under phoenixcontact.net/
products.