QUINT4-PS/12-24DC/5-15DC/2.5/PT
110260_en_00
PHOENIX CONTACT
23/30
12 Signaling
For signaling and the functional monitoring of the power
supply two LEDs and an active signal output are available.
Using the rotary selector select the required functional
monitoring. The monitoring of the output voltage (DC OK) or
the exceedance of the output power threshold are available
(P
Out
> P
Thr
).
12.1 Rotary selector switch in position DC OK:
In this switch position the output voltage (U
Out
) is monitored.
If the DC OK threshold is exceeded (U
Out
> 0.9 x U
Set
) the
green DC OK LED turns on. Additionally, the signal output
(SIG) "active high" is active. If the output voltage drops
below the DC OK threshold value (U
Out
< 0.9 x U
Set
), the
DC OK LED flashes. The signal output is switched to "active
low".
12.2 Rotary selector switch in position >50 %, >75 %
or boost >100 %:
In each of these switch positions the output power (P
Out
) is
monitored. When the set threshold is exceeded the yellow
LED lights up (P
Out
> P
Thr
) and the signal output (SIG)
switches to "active low".
12.3 Location and function of the signaling elements
Figure 19
Position of signaling elements
Key
The following table shows the standard assignment for signaling for the U/I characteristic curves which is set by default.
Figure 20
U/I signaling
No. Signaling elements
1
LED status indicator DC OK
LED on: U
Out
> 90% x U
Set
LED flashing: U
Out
< 90 % x U
Set
2
LED P
Out
> P
Thr
3
Active signal output
Boost > 100%
> 75%
> 50%
DC OK
P >P
Out
Thr
U
Out
Signal (SIG)
QUINT PO
WER
Or
d.No
.290xxx
SIG
−
3.1
2.2
2.1
Output DC
+
3
1
2
LED: P
> P
Out
Thr
Normal operation
BOOST
Overload operation
yellow
LED flashing
LED on
LED off
P
< P
Out
Thr
P
> P
Out
Thr
U
< 0.9 x U
Out
Set
Signal SIG: P
> P
Out
Thr
active high
active low
default
active low
LED: DC OK
Signal SIG: DC OK
active high
active high
green
default
active low