QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00
PHOENIX CONTACT
7 / 25
Status and diagnostic indicator / signal output P>P
n
Connection labeling
3.4
Switching output
Transistor output, active
Continuous load current
20 mA
LED status indicator
green
Status and diagnostic indicator / signal input Start
230V
Connection labeling
3.6
Low signal
Connection to SGnd with < 2.7 k
Ω
High signal
Open (> 200
k
Ω
between Start and SGnd)
Status and diagnostic indicator / signal input Start
120V
Connection labeling
3.7
Low signal
Connection to SGnd with < 2.7 k
Ω
High signal
Open (> 200
k
Ω
between Start and SGnd)
Status and diagnostic indicator / signal output Out
1
Connection labeling
3.5
Switching output
Transistor output, active
Status and diagnostic indicator / signal input Remote
Connection labeling
3.8
Low signal
Connection to SGnd with < 2.7 k
Ω
High signal
Open (> 35 k
Ω
between remote and SGnd)
Signal ground SGnd
Connection labeling
3.9
Function
Signal ground
Reference potential
For signal inputs and signal outputs
Signal connection data
Connection method
Screw connection
Conductor cross section, rigid
0.2 mm² ... 1.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule with plastic
sleeve
0.2 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil
30 ... 12
Stripping length
8 mm
Tightening torque
0.5 Nm ... 0.6 Nm