Observe the national safety and accident prevention
regulations.
–
Assembly and electrical installation must correspond to
the state of the art.
–
The inverter is a built-in device. The IP20 degree of
protection of the device is intended for use in a clean
and dry environment.
–
The device must be installed in a control cabinet that
can be locked and only opened by specialist staff.
–
Use in a CONTROLLED ENVIRONMENT - the unit is
intended for installation in a temperature-regulated,
indoor area that is relatively free of conductive
contaminants.
–
The housing can become hot, depending on the
ambient temperature and device load.
–
Observe the mechanical and thermal limits of the
device.
–
Ensure sufficient convection. Information on minimum
clearances to other devices is listed in the section:
Device dimensions and keep-out areas.
–
Ensure that the location is sufficiently ventilated.
–
Mount the device horizontally (standard mounting
position).
–
Use copper cables with an operating temperature of
75°C
(ambient temperature
55°C)
and
90°C (ambient temperature
75°C).
–
For the connection parameters, such
as the required
stripping length for wiring with and without ferrule, refer
to the technical data.
–
To reduce the risk of fire, connect only to a circuit
provided with the following maximum branch circuit
overcurrent protection in accordance with the National
Electrical Code, ANSI/NFPA 70.
–
To reduce the risk of fire, replace fuses only with those
that have the same type and rating. Relevant fuses can
be found in the accessories in the ordering data.
–
The device is maintenance-free. Repairs may only be
carried out by the manufacturer. Opening the housing
invalidates the warranty.
–
The inverter may only be used for its intended use.
–
Improper use invalidates the device protection.
–
Provide an easily reached switch/ fuse for wiring input
terminal close to the device at one pole of the DC
input,
which is marked as the disconnecting device for this
device (30
V
DC,
50
A, slow blow).
–
Ensure that no hazardous voltage in normal mode or
single fault case applies to all signal terminals and
communication interfaces.
–
Source connected to the inverter input must be SELV
circuits that can be either battery circuits or secondary
circuits derived from mains circuits of overvoltage
category CAT II up to 300
V and have to be separated
from mains circuits by double or reinforced insulation.
–
A suitable electrical and fire enclosure which provides
adequate mechanical rigidity shall be provided by the
end product.
–
When using a battery, follow the battery manufacturer's
instructions and ensure that the input data of the
inverter are observed.
–
The switching outputs are active outputs according to
SELV. These may only be operated on permitted SELV
circuits.
–
The permanent output power P
N
is limited at an ambient
temperature of 60°C. Observe the maximum output
powers for the respective operating conditions.
–
Keep these instructions in a safe place – this data sheet
contains important safety notes which must be
observed during installation and maintenance of the
device.
NOTE
More follows