QUINT4-INV/24DC/1AC/600VA/USB
108987_en_00
25 / 25
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
15
Derating
15.1
Ambient temperature
At an ambient temperature of up to
50°C, the inverter
supplies continuous nominal power. When operating the
inverter at an ambient temperature of
>50°C,
a power
derating of 2.5%/K
should be ensured.
Figure 23
Temperature-dependent derating
15.2
Installation height
The inverter can be operated at an installation altitude of up
to 2000
m without any limitations. Different data applies for
installation locations above 2000
m due to the differing air
pressure and the reduced convection cooling associated
with this.
A power derating of 0.6%/100 m should be observed for
installation heights between 2000 and 3000 m.
Figure 24
Altitude-dependent derating
T [°C]
A
[%]
50
60
70
80
90
100
P
Out
0
10
20
30
40
50
60
H [m]
[%]
P
Out
0
1000
2000
3000
80
85
90
95
100
105