Description

DC/AC inverter

QUINT4-INV/24DC/1AC/600VA/

USB

© PHOENIX CONTACT

Data sheet

The QUINT-INV DC/AC inverter is used for generating AC 

electricity in DC applications.

The output AC voltage RMS value can be configured via 

software from a total of nine values in two ranges. The range 

will be selected via the signal terminal during device startup.

The QUINT-INV can be connected in parallel to generate a 

redundant system, to increase power, or to generate a 3-

phase grid.

Can be used worldwide thanks to manual selection of 

AC output voltage via signal terminal

Pure sine curve at the output

Comprehensive signaling

Parallel connection possible (increased performance 

and redundancy, 3

 

AC)

Integrated USB interface

High efficiency

Technical data (short form)

Nominal input voltage

24 V

 

DC

Input voltage range

20 V

 

DC ... 30 V

 

DC

Current consumption

typ. 23 A / max. 28 A

Apparent power

600 VA

Real power

480 W

Nominal output voltage / Nominal 

output current , 100%

 

load

 

120 V

 

AC / 5 A 

( 100

 

V

 

AC

 

/

 

6

 

A...130

 

V

 

AC

 

/

 

4,6

 

A )

230 V

 

AC / 2.6 A 

( 200 V

 

AC /

 

3

 

A...240

 

V

 

/

 

2,5

 

A )

Output voltage tolerance ( no soft 

start )

±2

 

%

Nominal output frequency

60 Hz / 50 Hz

Output frequency tolerance

±0.5

 

%

Form of output voltage

Pure sine

Efficiency ( Nominal load )

> 86 % (120 V AC) / 

> 87 % (230 V

 

AC)

MTBF (IEC 61709, SN 29500)

532525 h (40

 

°C)

Ambient temperature (operation)

-25 °C ... 60 °C

Dimensions (W/H/D)

180 / 130 / 125 mm

Weight

2.5 kg

All technical specifications are nominal and refer to a room temperature of 25

 

°C and 70% relative humidity at 

2000

 

m above sea level.

108987_en_00

2020-09-28

Содержание QUINT1AC

Страница 1: ...ased performance and redundancy 3 AC Integrated USB interface High efficiency Technical data short form Nominal input voltage 24 V DC Input voltage range 20 V DC 30 V DC Current consumption typ 23 A max 28 A Apparent power 600 VA Real power 480 W Nominal output voltage Nominal output current 100 load 120 V AC 5 A 100 V AC 6 A 130 V AC 4 6 A 230 V AC 2 6 A 200 V AC 3 A 240 V 2 5 A Output voltage to...

Страница 2: ...mounting position 14 7 3 Mounting the inverter 14 7 4 Removing the inverter 15 7 5 Wall mounting 15 8 Device connection 17 8 1 Connection parameters 17 9 Device connection terminal blocks 17 9 1 DC input 17 9 2 AC output 18 9 3 Connection terminal block signaling 18 10 Interface 18 10 1 USB mini type B 18 11 Device operation 19 11 1 Setting the operating mode 19 11 2 Remote 19 11 3 Start 120 V Sta...

Страница 3: ...C 600VA USB 108987_en_00 PHOENIX CONTACT 3 25 14 Signaling 22 14 1 LED indicators and signal outputs 23 14 2 Signal outputs 24 14 3 Signal inputs 24 15 Derating 25 15 1 Ambient temperature 25 15 2 Installation height 25 ...

Страница 4: ...ed on the left right UWA 130 2901664 1 Universal wall adapter for securely mounting the device in the event of strong vibrations The device is screwed directly onto the mounting surface The universal wall adapter is attached on the top bottom UWA 182 52 2938235 1 Type 2 3 surge protection consisting of protective plug and base element with integrated status indicator and remote signaling for singl...

Страница 5: ...t plastic sleeve 0 2 mm 4 mm Conductor cross section AWG kcmil 30 10 Stripping length 8 mm Tightening torque 0 5 Nm 0 6 Nm Output data Apparent power 600 VA Real power 480 W Power factor cos phi 0 8 Nominal output voltage Nominal output current 100 load 120 V AC 5 A 100 V AC 6 A 130 V AC 4 6 A 230 V AC 2 6 A 200 V AC 3 A 240 V 2 5 A Output voltage tolerance no soft start 2 Nominal output frequency...

Страница 6: ...lexible with ferrule without plastic sleeve 0 2 mm 4 mm Conductor cross section AWG kcmil 30 10 Stripping length 8 mm Tightening torque 0 5 Nm 0 6 Nm Status and diagnostic indicator signal output Alarm Connection labeling 3 1 Switching output Transistor output active Output voltage 24 V Continuous load current 20 mA LED status indicator red Status and diagnostic indicator signal output AC OK Conne...

Страница 7: ...stic indicator signal output Out 1 Connection labeling 3 5 Switching output Transistor output active Status and diagnostic indicator signal input Remote Connection labeling 3 8 Low signal Connection to SGnd with 2 7 kΩ High signal Open 35 kΩ between remote and SGnd Signal ground SGnd Connection labeling 3 9 Function Signal ground Reference potential For signal inputs and signal outputs Signal conn...

Страница 8: ...egory according to EN 61010 2 201 II MTBF IEC 61709 SN 29500 532525 h 40 C Degree of protection Protection class IP20 I Dimensions W H D 180 130 125 mm Weight 2 5 kg Ambient conditions Ambient temperature operation 25 C 60 C Derating Output power 50 C 2 5 K Ambient temperature storage transport 40 C 85 C Humidity non condensing 95 Installation height 3000 m Derating Output power 2 000 m 0 6 100 m ...

Страница 9: ...urst EN 61000 4 4 Input 2 kV 2 kV DC input 2 kV 2 kV Output 2 kV 2 kV Signal 2 kV 2 kV Signal USB 2 kV Comments Criterion B Criterion A B for USB Surge voltage load surge EN 61000 4 5 Input 1 kV symmetrical 2 kV asymmetrical 1 kV symmetrical 2 kV asymmetrical Output 1 kV symmetrical 2 kV asymmetrical 2 kV symmetrical 4 kV asymmetrical Signal 1 kV asymmetrical 1 kV asymmetrical Comments Criterion B...

Страница 10: ...trol cabinet Keep flames embers or sparks away from the module Provide a switch circuit breaker close to the device at the DC input and the AC output respectively which are marked as the disconnecting device for this device This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety measures that follow this symbol to avoid possible personal injurie...

Страница 11: ...re replace fuses only with those that have the same type and rating Relevant fuses can be found in the accessories in the ordering data The device is maintenance free Repairs may only be carried out by the manufacturer Opening the housing invalidates the warranty The inverter may only be used for its intended use Improper use invalidates the device protection Provide an easily reached switch fuse ...

Страница 12: ...llel Port 5 2 DC OK 15 1 14 13 12 11 10 8 7 6 5 4 3 2 9 No Designation Connection labeling 1 PE N bridge connection terminal blocks 2 4 1 3 2 Universal DIN rail adapter rear of housing 3 Signaling connection terminal blocks 3 1 3 9 4 LED parallel run 5 Communication interface parallel run 5 2 6 Rotary selector switch parallel run mode Operating mode 7 LED status indicator Alarm 8 Rotary selector s...

Страница 13: ... K 3 3 P P n 3 4 O u t 1 3 5 S ta rt 2 3 0 V 3 6 S ta rt 1 2 0 V 3 7 R e m o te 3 8 S G n d 3 9 L1 Slave L1 Master L1 Master Soft Start L3 L2 Single Redundancy Power 3AC Link Parallel Port 5 2 5 1 130 50 50 180 DC OK 125 132 5 C 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 2 1 2 2 2 3 1 1 1 2 5 1 5 2 Output AC N L PE Alarm AC OK DC OK P Pn Out 1 Start 230V Start 120V Remote SGnd Input DC Parallel PE N Port...

Страница 14: ...n To ensure sufficient convection maintain an adequate minimum clearance between the inverter and above below the installed devices For information on the required minimum clearances refer to the section Device dimensions and keep out areas Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm DC OK 3A C Link Po we r Sing le Re dunda...

Страница 15: ...tremely high level of mechanical stability is ensured 7 5 1 Mounting the UWA 182 52 universal wall adapter Proceed as follows to disassemble the universal DIN rail adapter that comes pre mounted 1 Remove the screws for the universal DIN rail adapter using a suitable screwdriver Torx 10 2 Remove the universal DIN rail adapter from the rear of the device 3 Position the universal wall adapter in such...

Страница 16: ...versal DIN rail adapter from the rear of the device 3 Position the two piece universal wall adapter on the right and left side of the housing 4 Insert the Torx screws into the appropriate hole pattern on the universal wall adapter so that the necessary mounting holes of the device can be accessed 5 Screw the two piece universal wall adapter onto the device Figure 9 Mounting the UWA 130 universal w...

Страница 17: ...e output voltage supply system configuration mm 0 2 4 0 2 4 0 2 4 0 2 1 5 Input DC 1 1 1 2 Output AC 2 1 2 3 Signals 3 1 3 9 N 2 4 PE 1 3 Screw 0 2 6 0 2 6 0 2 6 0 2 1 5 mm 0 2 4 0 2 4 0 2 4 0 2 1 5 mm mm 0 2 4 0 2 4 0 2 4 0 2 1 5 Cu 30 10 30 10 30 10 30 12 8 8 8 8 L mm 0 5 0 6 0 5 0 6 0 5 0 6 0 5 0 6 Nm lb in 5 7 5 7 5 7 5 7 AWG Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 ...

Страница 18: ...ommunicating with a PC or a higher level controller Figure 14 Service USB interface Mini type B device bottom 5 1 Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm 3A C Lin k Po we r Sin gle Re dundanc y AC OK P Pn Re mote L1 Slav e L1 L1 L2 L3 M aster M aster So ft Sta rt Pa rallel Po rt 5 2 L N 2 1 2 2 2 3 Outpu t AC 12 0 23 0V...

Страница 19: ...ion L1 Slave 1st slave device in the mode 3AC switch position L2 2nd slave device in the mode 3AC switch position L3 Master device in the mode 3AC with inclined start characteristic curve switch position L1 Master Soft Start Only applicable in 3AC operation at 230 V output voltage In this switch position the output voltage drops briefly during startup Figure 17 Rotary selector switch parallel run ...

Страница 20: ... or 240 V 50 Hz default or 60 Hz 12 3 Input voltage setting options You can set the following DC input voltage parameters via the POWER MANAGEMENT SUITE software Lower DC input voltage limit 20 V DC 26 5 V DC default 20 V DC Upper DC input voltage limit 28 V DC 30 V DC default 30 V DC Activation threshold 20 5 V DC 27 V DC default 23 V DC Note that the activation threshold must be at least 0 5 V h...

Страница 21: ...ions on grounding the neutral conductor In the delivery state this is ensured through the pre installed bridge in terminals 2 4 and 1 3 During parallel operation the following settings are transferred from the master device to the slave device The settings of the slave device are ignored here Remote signal terminal operation Settings via the POWER MANAGEMENT SUITE configuration software Changes to...

Страница 22: ... level control system Figure 21 LED indicators Alarm DCOK ACOK Out1 P Pn Start230V Start120V Remote SGnd 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 QUINT AC INV 600VA Alarm DC OK 3A C Link Po we r Sing le Re dundancy AC OK P Pn Re mote L1 Slav e L1 L1 L2 L3 M aster M aster So ft Start Pa rallel Po rt 5 2 L N 2 1 2 2 2 3 Outpu t AC 12 0 23 0V N 2 4 1 3 5 1 23 0V 12 0V 1 1 1 2 Inpu t DC 24 V AC OK P Pn Rem...

Страница 23: ...h high high high low high low low low high low high low low low high low low low low high high high low active low Alarm AC OK high high P Pn Note Device start input voltage too low too high Initialization LED test 3 sec Device off Device start Device start alarm output off alarm Output off remote contact connected to SGnd alarm Output on overload Output on alarm Output on Device start input voltag...

Страница 24: ... permanently depending on the detected voltage range You can assign other additional information to this signal output using the POWER MANAGEMENT SUITE software P Pn If the output power exceeds the maximum permitted output power the signal output is active high level The signal status can be inverted via the POWER MANAGEMENT SUITE software A digital transistor output is available as a signal conta...

Страница 25: ...Figure 23 Temperature dependent derating 15 2 Installation height The inverter can be operated at an installation altitude of up to 2000 m without any limitations Different data applies for installation locations above 2000 m due to the differing air pressure and the reduced convection cooling associated with this A power derating of 0 6 100 m should be observed for installation heights between 20...

Отзывы: