Power supply connection
Supply the Inline Controller using external 24 V DC voltage sources. The permissible
voltage ranges from 19.2 V DC to 30 V DC (ripple included).
The power consumption of the Inline Controller at 24 V is typically 4.8 W (no local bus
devices connected).
1.
Connect the power supplies to the connector for power supply as shown in Figure 2-23.
2.
Insert the connector in the Inline Controller.
3.
Switch on the power supplies.
4.
The UL, UM, and US LEDs light up and, after around 10 seconds, the FR and RDY
LEDs start flashing.
The Inline Controller is now fully initialized.
If the LEDs do not light up or start flashing, there is a serious error on the Inline Controller.
Please contact Phoenix Contact.
Figure 2-23
Supply voltage connection
Only use power supplies that are suitable for operation with capacitive loads (increased
inrush current) (see "Sizing of the power supply" on page 2-29).