2.8
Reset button (concealed)
The reset button (see item 3 in Figure 2-5 on page 2-6 or item 4 in Figure 2-6 on page 2-7)
on the Inline Controller can only be operated with a pin and is therefore protected against
accidental activation.
Pressing the reset button causes a complete reset of the Inline Controller.
If you carry out a voltage reset at the same time as you press the reset button, this resets
the Inline Controller to its default settings.
2.9
Parameterization memory
The parameterization memory can be used to save programs and configurations, which
belong to your project. In addition, application-specific data can also be stored on the
parameterization memory. See "Parameterization memory and Internet Explorer" on
page 3-6.
ILC 130 ETH
,
ILC 150 ETH,
ILC 155 ETH
The ILC 130 ETH, ILC 150 ETH and ILC 155 ETH Inline Controllers have an integrated
parameterization memory.
ILC 170 ETH 2TX
The ILC 170 ETH 2TX Inline Controller has a plug-in parameterization memory in the form
of an SD card. This plug-in parameterization memory is essential for operating the Inline
Controller. The parameterization memory is available in the following size.
NOTE:
Operation without parameterization memory is not permitted
Only insert and remove the parameterization memory when the Inline Controller supply
voltage is disconnected.
The parameterization memory must not be removed during operation of the Inline
Controller.
NOTE:
Use only a parameterization memory provided by Phoenix Contact:
256 MB parameterization memory:
SD FLASH 256MB
Order No. 2988120
NOTE: Parameterization memory (SD card) – formatting note
The SD card is preformatted and designed for use with Phoenix Contact devices. Ensure
that the SD card is not reformatted.
The parameterization memory is recognized during initialization of the Inline Controller.
Ensure that the parameterization memory has been inserted before switching on the