Technical Data
General
Housing dimensions (width x height x depth) 12.2 mm x 120 mm x 71.5 mm
(0.480 in. x 4.724 in. x 2.815 in.)
Weight
47 g (without connector)
Operating mode
Process data operation with 2 words
Connection method for the sensors
2-wire and 3-wire technology
Power supply for the sensors
With an external power supply or with an additional
segment terminal with a fuse (IB IL 24 SEG/F)
Permissible temperature (operation)
-25°C to +55°C (-13°F to +131°F)
Permissible temperature (storage/transport) -25°C to +85°C (-13°F to +185°F)
Permissible humidity (operation)
75%, on average, 85%, occasionally
In the range from -25°C to +55°C (-13°F to +131°F) appropriate measures against
increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport)
75%, on average, 85%, occasionally
For a short period, slight condensation may appear on the housing if, for example, the
terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation)
80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
Permissible air pressure (storage/transport) 70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level)
Degree of protection
IP 20 according to IEC 60529
Class of protection
Class 3 according to VDE 0106, IEC 60536
Deviations From Common Technical Data That Are Indicated in the IB IL SYS PRO UM E
User Manual
Noise Immunity Test According to EN 50082-2
Electrostatic discharge (ESD) according to
IEC 61000-4-2
Criterion B
6 kV contact discharge
6 kV air discharge
Mechanical Demands
Shock test according to IEC 60068-2-27,
IEC 60068-2-27
15g load for 11 ms, half sinusoidal wave,
three shocks in each space direction and orientation
25g load for 6 ms, half sinusoidal wave,
three shocks in each space direction and orientation