Measuring range 0 V through 10 V
Measuring range 0 mA through 20 mA
Measuring range -10 V t10 V
Measuring range -20 mA t20 mA
Input Data Word
(Two’s Complement)
0 V Through 10 V
U
Input
hex
dec
V
8001
Overrange
>
+10.837
2A55
10837
+10.837
2710
10000
+10.0
0001
1
+0.001
0000
0
≤
0
Input Data Word
(Two’s
Complement)
0 mA Through 20 mA
I
Input
hex
dec
mA
8001
Overrange
>
+21.674
54AA
21674
+21.674
4E20
20000
+20.0
0001
1
+0.001
0000
0
≤
0
Input Data Word
(Two’s Complement)
-10 V Through
+10 V
U
Input
hex
dec
V
8001
Overrange
>
+10.837
2A55
10837
+10.837
2710
10000
+10.0
0001
1
+0.001
0000
0
0
FFFF
-1
-0.001
D8F0
-10000
-10.0
D5A6
-10837
-10.837
8080
Below range
<-10.837
Input Data Word
(Two’s Complement)
-20 mA Through
+20 mA
I
Input
hex
dec
mA
8001
Overrange
>
+21.674
54AA
21674
+21.674
4E20
20000
+20.0
0001
1
+0.001
0000
0
0
FFFF
-1
-0.001
B1E0
-20000
-20.0
A656
-21674
-21.674
8080
Below range
<-21.674