IB IL 24 AI 2/SF-230
24
6232A
Measuring range 4 mA through 20 mA
Example
Measured value representation in different data formats.
Measuring range:
0 mA through 20mA
Measured value:
10 mA
Input data word:
Input Data Word
(Two’s Complement)
4 mA Through 20 mA
I
Input
hex
dec
mA
8001
Overrange
>
21.339
43BB
17339
21.339
3E80
16000
20.0
0001
1
4.001
0000
0
4.0 through 3.2
8002
Open circuit
< 3.2
Format
HEX Value
DEC Value
Measured Value
IB IL
3A98
15 000
10 mA
IB ST
4000
16 384
10 mA
IB RT
4000
16 384
10 mA
Standardized display
2710
10 000
10 mA