Connecting and Grounding
•
The controller warms up during operation, and should therefore be installed on a non flammable surface only.
•
Connect wires in indicated order 1 2 3 4 5 6 7 to avoid any installation faults
•
To avoid any damaging voltage on the wires, first connect the wire to the controller, then to the load, to the battery or to the panel.
•
Minimum recommended wire size: 4 mm²
•
Make sure the wire length between battery and controller is as short as possible
•
Be aware that all negative wires of CIS-N-MPPT-LED 85/15 are connected together and therefore have the same electrical potential. If any
grounding is required further to the casing, always do this on the negative wires.
•
Grounding of the casing is done by the grounding post on the left side.
•
Maximum cable length from charge controller to LEDs: < 2m
Function
Wire size (cross section)
Color
①
Positive wire LED output
AWG 20 (0.5 mm
2
)
Red
②
Negative wire LED output
AWG 20 (0.5 mm
2
)
Blue
③
Negative battery terminal
AWG 13 (2.5 mm
2
)
Black
④
Positive battery terminal
AWG 13 (2.5 mm
2
)
Red
⑤
Negative panel terminal
AWG 13 (2.5 mm
2
)
Black
⑥
Positive panel terminal
AWG 13 (2.5 mm
2
)
Yellow
⑦
Input for PIR motion sensor
AWG 24 (0.25 mm
2
)
Black
Содержание CIS-N-MPPT-LED 85/15
Страница 7: ...www phocos com 6 P a g e Erdungsbolze Eingang für PIR Bewegungsmelder Sicherung ...
Страница 20: ...www phocos com 19 P a g e Fuse Grounding post Input for PIR motion sensor ...
Страница 33: ...www phocos com 32 P a g e Punto de puesta a tierra Entrada PIR para sensor de movimiento Fusible ...
Страница 46: ...www phocos com 45 P a g e Entrée PIR pour détecteur de mouvement Fusible Mise à la terre ...
Страница 58: ...www phocos com 57 P a g e Ponto de aterramento Entrada para sinal de sensor de movimento Fusível ...
Страница 71: ...www phocos com 70 P a g e 外壳接地端子 功率调节功能短时取消 信号输入 保险丝 ...