Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
Philips Lighting Canada Ltd.
281 Hillmount Road,
Markham ON, Canada L6C 2S3
Phone: 800-668-9008
9140053550 February 2016
shield and place it over the backbox and EXIT sign assembly. Place sheetmetal trim ring over the clear
plastic shield and secure both to the backbox using the supplied tamperproof Torx screws.
OPERATING INSTRUCTIONS
(NON-DIAGNOSTICS EQUIPPED UNITS)
(FOR SELF-DIAGNOSTICS EQUIPPED UNITS, SEE NEXT
PAGE)
1.
Energize AC power to the equipment and check that the test switch/pilot lamp illuminates and
EXIT is illuminated.
2.
Press the test switch/pilot lamp and verify that the pilot lamp turns off and EXIT remains
illuminated.
3.
Leave AC connected for a minimum of 24 hours before performing any extended testing. Full
recharge of batteries may require one full week.
Notes:
1.
This equipment is provided with a lockout feature whereby connecting battery leads prior to
energizing AC power will not turn on the EXIT. After AC power is energized, the EXIT will
illuminate upon AC power failure.
2.
This equipment is provided with a low battery disconnect feature which prevents full discharge
of the batteries. If the building is to be unoccupied for an extended period of time and AC power
is shut off, the batteries should be disconnected from the charger to prevent damage.
3.
The batteries provided in this equipment are sealed and require no maintenance