Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
Philips Lighting Canada Ltd.
281 Hillmount Road,
Markham ON, Canada L6C 2S3
Phone: 800-668-9008
9140053550 February 2016
STEP 2 for Canopy Mounting (Wall or Ceiling) –
Attach cross bar found in canopy kit to a 3-1/2” or single gang junction box. Pull the buildings AC
service wiring thru the center hole in the cross bar. Fasten the canopy to the cross bar using the two #8-
32 x ½” screws provided in the canopy kit. Pull the buildings AC service wiring thru the center hole in
the canopy. Remove one of the two knockouts that are found in the side or top of the backplate or extra
stencil face (use the extra stencil face for double sided “EXIT” installations – single face installation using
a blank backplate is shown above). Place the resulting opening in the backplate or stencil over the
threaded nipple on the canopy and thread on the jamb nut. A four pole connector assembly is provided
on the stencil/electronics assembly for AC service connection. Make AC service connections according to
the table below. Snap stencil/electronics assembly to backplate or extra stencil and refer to operating
instructions section.
230VAC
120VAC
Green Wire - Ground
Green Wire - Ground
White Wire - Common White Wire - Common
Black Wire – Cap Off
Black Wire – 120VAC
Blue Wire – 230VAC
Blue Wire – Cap Off
Green - Ground
CAUTION: Unused primary wire must be capped off!