Check the following list.  If you are still unable to rectify the situation, contact your nearest Dynalite office.  A 
complete list of distributors worldwide can be found on the Internet at: 

www.philips.com/dynalite

 

Please ensure that you have completed the following prior to calling our technical support department. 

 

Check all symptoms in the Troubleshooting list 

 

Check for any deviations between the installation and the installation instructions 

 

Make a list of the model numbers of all devices used in the system 

 

 

 

SYMPTOM 

PROBABLE CAUSE 

ACTION 

Load Controller does not operate at all. No Service 
LED  activity.  Power  supply  indicator  LED  on  PCB 
not lit. 

Incorrect  connection  of  Mains  supply,  or  no 
power available. 

Check  power  supply  to  Load  Controller.    Check 
Line and Neutral input connections. 

Power supply indicator LED lit, but no Service LED 
activity. 

Supply  voltage  too  low,  short  circuit  on 
network.  Control PCB faulty. 

Check  supply  voltage  is  at  least  75%  of  rated 
voltage.    Check  5V  &  12V  terminal  voltages,  5V 
supply must be present. Disconnect network bus 
and restore power.  Replace control PCB. 

Load  Controller  will  not  respond  to  control  panel 
push buttons. 

Control  panel  incorrectly  wired  or  incorrect 
configuration. 

Check operation of LEDs on control panel.  Push 
button  on  panel  and  study  response  of  service 
LED. 

Load  Controller  operates  properly  but  circuit 
breakers keep tripping. 

Instant tripping: - short circuit on load.  
Delayed tripping: - Load Controller overloaded. 

Check load wiring for short circuits. 
Verify Load Controller loading with current tester 
(don’t forget to de-rate for low power-factor loads 
and  transformer  losses).  Check  that  the  breaker 
terminals are tight. 

Fluorescent lights won’t dim. 

Wrong  type  of  ballast  or  ballast  incorrectly 
wired.  Control  cable  from  DRC810DT  to 
ballasts not installed. 

Check  ballast type.    Check  actual  wiring  against 
ballast manufacturer’s diagram. Check 1-10V/DSI 
cable and settings. 

 

 

Supply: 

230V ±14% 50/60Hz Single Phase at 40A 

Outputs: 

2 x dimmed outputs (leading edge phase control) at 20A, total box load is 40A max 

Power Conditioning: 

- Regulated outputs 
- Over voltage protection 
- Surge protection 
- Brownout/Sag protection 
- Spike protection 
- Soft start 
- 16 bit fade resolution (65535 steps) 

Maximum Total Box Load: 

40A 

Regulating Device: 

Dual SCRs - 800V 65A nom. 800A surge 

Control Inputs: 

1 x RS485 DyNet/DMX512 serial port 
1 x programmable AUX dry contact input 

User Controls: 

Service/Override Switch  
Diagnostic LED  
Hardware override switch on each channel 

Internal Controls:  

Programmable Logic Controller 
Dynalite Accessory Module enabled 

DyNet DC VE: 

200mA (Supply for approx 10 panels) 

Preset Scenes: 

170 

Supply Terminals: 

Line1, Neutral, Earth, - 1 x 25mm2 max conductor size 

Output Terminals: 

Line, Neutral for each channel - 1 x 10mm2 max conductor size, Earth Link bar provided 

Cable Entries: 

Mains - 5 x 25mm2 knockouts on a 105mm x 145mm removable gland plate 
Data - 1 x 25mm2 dia. knockout 

Diagnostic Functions: 

 

Device Online/Offline status 
Circuit breaker trip reporting (optional) 
Channel override switches 

Compliance: 

CE, C-Tick 

Construction: 

Aluminium/Steel wall mount case with epoxy finish 

Dimensions: 

H 285mm x W 210mm x D 150mm  
(excludes wall brackets) 

Weight: 

4.2kg 

troubleshooting 

 

DRC220-S Installation Manual Rev F.doc Specifications and design subject to change without notice. 

Dynalite Manufactured by WMGD Pty Ltd (ABN 33 097 246 921). All rights reserved. Dynalite, Dimtek, DyNet and DLight and associated logos are the 

registered trademarks of Dynalite Intelligent Light Pty Ltd.  Not to be reproduced without permission. 

Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333 

E-mail: 

[email protected]

             Web: Philips.com/dynalite

 

 

Содержание Dynalite DLE220-S

Страница 1: ...alite info philips com ABN 33 097 246 921 philips com dynalite DLE220 S 2 x 20A Leading Edge Dimmer Installation Manual Contents Features 2 Troubleshooting 7 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Hardware Controls Analogue Inputs 7 ...

Страница 2: ...will allow any control panel to control all channels in all dimmers Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earth...

Страница 3: ...DLE220 S Instruction Manual Rev F doc 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE220 S internal view ...

Страница 4: ...re designed to accommodate 4 fixing screws up to 8mm diameter The DLE220 S can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control cab...

Страница 5: ... 10mm2 cables Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 20A Derate for reactive loads Energising the Device If it is necessary to energise load circuits before any control cables are connected it is acceptable to replace the cover and energise the device immediately as the default factory programming is to have all channels set t...

Страница 6: ... VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting method is...

Страница 7: ...no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for optional fea...

Страница 8: ...allast incorrectly wired Control cable from DRC810DT to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings Supply 230V 14 50 60Hz Single Phase at 40A Outputs 2 x dimmed outputs leading edge phase control at 20A total box load is 40A max Power Conditioning Regulated outputs Over voltage protection Surge protection ...

Отзывы: