8
DLE220-S Instruction Manual Rev F.doc
Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite office. A
complete list of distributors worldwide can be found on the Internet at:
www.philips.com/dynalite
Please ensure that you have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
SYMPTOM
PROBABLE CAUSE
ACTION
Load Controller does not operate at all. No Service
LED activity. Power supply indicator LED on PCB
not lit.
Incorrect connection of Mains supply, or no
power available.
Check power supply to Load Controller. Check
Line and Neutral input connections.
Power supply indicator LED lit, but no Service LED
activity.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Check supply voltage is at least 75% of rated
voltage. Check 5V & 12V terminal voltages, 5V
supply must be present. Disconnect network bus
and restore power. Replace control PCB.
Load Controller will not respond to control panel
push buttons.
Control panel incorrectly wired or incorrect
configuration.
Check operation of LEDs on control panel. Push
button on panel and study response of service
LED.
Load Controller operates properly but circuit
breakers keep tripping.
Instant tripping: - short circuit on load.
Delayed tripping: - Load Controller overloaded.
Check load wiring for short circuits.
Verify Load Controller loading with current tester
(don’t forget to de-rate for low power-factor loads
and transformer losses). Check that the breaker
terminals are tight.
Fluorescent lights won’t dim.
Wrong type of ballast or ballast incorrectly
wired. Control cable from DRC810DT to
ballasts not installed.
Check ballast type. Check actual wiring against
ballast manufacturer’s diagram. Check 1-10V/DSI
cable and settings.
Supply:
230V ±14% 50/60Hz Single Phase at 40A
Outputs:
2 x dimmed outputs (leading edge phase control) at 20A, total box load is 40A max
Power Conditioning:
- Regulated outputs
- Over voltage protection
- Surge protection
- Brownout/Sag protection
- Spike protection
- Soft start
- 16 bit fade resolution (65535 steps)
Maximum Total Box Load:
40A
Regulating Device:
Dual SCRs - 800V 65A nom. 800A surge
Control Inputs:
1 x RS485 DyNet/DMX512 serial port
1 x programmable AUX dry contact input
User Controls:
Service/Override Switch
Diagnostic LED
Hardware override switch on each channel
Internal Controls:
Programmable Logic Controller
Dynalite Accessory Module enabled
DyNet DC VE:
200mA (Supply for approx 10 panels)
Preset Scenes:
170
Supply Terminals:
Line1, Neutral, Earth, - 1 x 25mm2 max conductor size
Output Terminals:
Line, Neutral for each channel - 1 x 10mm2 max conductor size, Earth Link bar provided
Cable Entries:
Mains - 5 x 25mm2 knockouts on a 105mm x 145mm removable gland plate
Data - 1 x 25mm2 dia. knockout
Diagnostic Functions:
Device Online/Offline status
Circuit breaker trip reporting (optional)
Channel override switches
Compliance:
CE, C-Tick
Construction:
Aluminium/Steel wall mount case with epoxy finish
Dimensions:
H 285mm x W 210mm x D 150mm
(excludes wall brackets)
Weight:
4.2kg
troubleshooting
DRC220-S Installation Manual Rev F.doc Specifications and design subject to change without notice.
Dynalite Manufactured by WMGD Pty Ltd (ABN 33 097 246 921). All rights reserved. Dynalite, Dimtek, DyNet and DLight and associated logos are the
registered trademarks of Dynalite Intelligent Light Pty Ltd. Not to be reproduced without permission.
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-mail:
Web: Philips.com/dynalite