Determine Your Requirements

 

Serial  Ports  are  used  to  interconnect  other 
dimmers,  smart  control  panels,  sensors  and 
AV  controllers.    Serial  port  devices  can  be 
identified  by  4  terminals,  labelled:  GND, 
DATA+, DATA-, +VE. 
 

Serial Cable Connections 

There is one RS485 port for DyNet signals, in 
the form of a RJ12 socket, on the front panel, 
which is used for the temporary connection of 
a  PC  or  a  Portable  Programmer.  There  are 
data  terminals  on  the  control  card,  for 
permanent  connections.    The  recommended 
cable  for  connections  to  the  serial  port  is 
screened,  stranded  RS485  data  cable  with 
three  twisted  pairs.  Recommended  cable 
types include: 

Belden:   

9503 

Dynalite:   

DYNET-STP-CABLE 

Garland:   

MCP3S 

Hartland:   

HCK603 

M&M Cable: 

B2003CS 

M&M Cable: 

B9503CS 

Multicables: 

AWM E120236 2092 20 

RS Components: 

368-687 

Dynalite   

DYNET-STP-CABLE 

One  pair  is  paralleled  for  GND,  one  pair  paralleled  for  +VE, 
and one pair used for DATA+ and DATA-.  

 

Recommended Cable Colour Coding 

Green/White pair 

paralleled for GND 

Orange/White pair 

paralleled for +VE 

Blue/White pair 

Blue for DATA+ 

 

 

 

White for DATA- 

Brown/White pair 

Spare or for Join  

The colour-coding scheme used is not critical, 
as  long  as  the  same  scheme  is  used 
throughout the installation. 
 

Serial Cable Connecting Method 

The  recommended  connecting  method  is  to 
‘daisy  chain’  devices  (ie.  starting  at  the  first 
device,  then  looping  in  then  out  of  devices, 
with  a  single  cable  terminating  at  the  last 
device.  There  should  not  be  any  spurs  or 
stubs,  and  only  the  first  and  last  device 
should  terminate  1  cable,  all  other  devices 
should  terminate  2  cables).  Devices  may  be 
wired  in  any  order.    The  Data  Cable  should 
be  segregated  from  any  Mains  Cables  by 
30mm.  

A data cable that is connected to an 

energised  dimmer  is  live.  Do  not  cut  or 
terminate  live  data  cables

.    If  the  data  cable 

has to cross over any mains cables, it should 
do so at a 90° angle. 

Connect Data Cable in a ‘Daisy Chain’ 

RJ12 Socket Connections 

Serial Cable Permanent Connections 

 

connecting serial control cable 

 

Содержание Dynalite DLE220-S

Страница 1: ...alite info philips com ABN 33 097 246 921 philips com dynalite DLE220 S 2 x 20A Leading Edge Dimmer Installation Manual Contents Features 2 Troubleshooting 7 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Hardware Controls Analogue Inputs 7 ...

Страница 2: ...will allow any control panel to control all channels in all dimmers Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earth...

Страница 3: ...DLE220 S Instruction Manual Rev F doc 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE220 S internal view ...

Страница 4: ...re designed to accommodate 4 fixing screws up to 8mm diameter The DLE220 S can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control cab...

Страница 5: ... 10mm2 cables Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 20A Derate for reactive loads Energising the Device If it is necessary to energise load circuits before any control cables are connected it is acceptable to replace the cover and energise the device immediately as the default factory programming is to have all channels set t...

Страница 6: ... VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting method is...

Страница 7: ...no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for optional fea...

Страница 8: ...allast incorrectly wired Control cable from DRC810DT to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings Supply 230V 14 50 60Hz Single Phase at 40A Outputs 2 x dimmed outputs leading edge phase control at 20A total box load is 40A max Power Conditioning Regulated outputs Over voltage protection Surge protection ...

Отзывы: