Select a Suitable Location

 

This device is designed for indoor use only.  If 
installing in an external location, the DLE220-
S must be housed in a suitable well-ventilated 
enclosure.  Choose a dry location, that will be 
accessible  after  the  installation  is  complete.  
The DLE220-S should be mounted 

vertically, 

the right way up

.  The DLE220-S requires an 

air gap of 100mm on each side and at the top 
and  bottom  of  the  device.    This  air  gap  is 
required  to  ensure  serviceability  of  the 
DLE220-S without complete removal from the 
mounting  surface.    This  device  may  emit 
some  mechanical  noise.    Take  this  into 
account when deciding the mounting location. 

 

 
 

Fixing the Device 

The  DLE220-S  has  four  mounting  brackets 
that attach to the rear of the enclosure.  The 
brackets  are  designed  to  accommodate  4 
fixing  screws  up  to  8mm  diameter.    The 
DLE220-S  can  be  fixed  to  the  wall  without 
opening  the  cabinet  or  removing  covers.  
Make sure no dust or other debris enters the 
device  during  installation.    Do  not  leave  the 
front  cover  off  for  any  length  of  time.  
Excessive  dust  and  dirt  can  degrade  the 
cooling of internal components. 

 

 
 

Allow for Cable Entry 

Supply, load and load control cables enter the 
enclosure at the top.  If these cables are fed 
from  below  the  mounting  position,  they 
should  be  routed  around  the  enclosure  to 
enter at the top.  An alternative method is to 
stand  the  enclosure  off  from  the  mounting 
surface  by  mounting  it  on  a  cable  tray  or  a 
Unistrut  style  product.    The  cables  can  then 
be  routed  between  the  enclosure  and  the 
mounting surface, and enter the enclosure via 
the  cut-out  provided  on  the  mounting  face.  
The control cables enter at the bottom of the 
enclosure.    Control  cables  should  never  be 
run  in  the  mains  voltage  sections  of  the 
enclosure. 

mounting 

 

Содержание Dynalite DLE220-S

Страница 1: ...alite info philips com ABN 33 097 246 921 philips com dynalite DLE220 S 2 x 20A Leading Edge Dimmer Installation Manual Contents Features 2 Troubleshooting 7 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Hardware Controls Analogue Inputs 7 ...

Страница 2: ...will allow any control panel to control all channels in all dimmers Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earth...

Страница 3: ...DLE220 S Instruction Manual Rev F doc 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE220 S internal view ...

Страница 4: ...re designed to accommodate 4 fixing screws up to 8mm diameter The DLE220 S can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control cab...

Страница 5: ... 10mm2 cables Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 20A Derate for reactive loads Energising the Device If it is necessary to energise load circuits before any control cables are connected it is acceptable to replace the cover and energise the device immediately as the default factory programming is to have all channels set t...

Страница 6: ... VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting method is...

Страница 7: ...no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for optional fea...

Страница 8: ...allast incorrectly wired Control cable from DRC810DT to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings Supply 230V 14 50 60Hz Single Phase at 40A Outputs 2 x dimmed outputs leading edge phase control at 20A total box load is 40A max Power Conditioning Regulated outputs Over voltage protection Surge protection ...