background image

Connecting Serial Control Cables 

 

 

DBC1205 Installation Manual Rev J.docx   

7

 

AUX Input 

- This is a dry contact interface that is active low.  The dry contact is connected between the 

AUX and GND terminals on the DyNet connector strip.  The function of the AUX input is programmable.  
Ensure that the cable length between the dry contact and terminal strip is no longer than 2 metres.

 

 
Service LED

 - The Service LED has 3 signalling modes, which are useful for troubleshooting:

 

Blinking slowly (1Hz) = Normal Operation 
Blinking fast (4Hz) = Network Activity Detected 
On = Fault 
 

Service Switch

 - The Service Switch has three functions: 

1 push = Transmit Network ID 
3 pushes = All Channels 100% 
Push & hold for 4 sec = Reboot 
 

Top Set

 - This adjusts the maximum output that all other control sources can select, ie: if the Top Set is 

fully  clockwise,  100%  selected  by  a  control  source  will  give  100%  output.    If  it  is  fully  anti-clockwise, 
100%  selected  by  a  control  source  will  give  50%  output.  This  control  is  useful for  extending  lamp life 
and  can  be  operated  without  any  form  of  network  control,  effectively  turning  the  device  into  a  stand-
alone power conditioner and lamp protector. 
 

Accessory Module Socket

 - Accepts plug in modules for optional features such as DMX512 ports and 

Time clocks. Consult your distributor for details on the available accessory modules. 

Содержание Dynalite DBC1205

Страница 1: ...ynalite info philips com ABN 33 097 246 921 Philips com dynalite DBC1205 12 x 5A HF Ballast Controller Installation Manual Contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 ...

Страница 2: ...r for details Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not ex...

Страница 3: ...internal view DBC1205 Installation Manual Rev J docx 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DBC1205 ...

Страница 4: ... brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DBC1205 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of the internal components Allow for Cable Entry Supply and load ca...

Страница 5: ... must be individually connected to the neutral link terminals inside the cabinet Never use a common neutral at a remote location Load Control Cables Load control cables can be terminated on the 2 x 12 way terminal strips located directly above the load terminals The left terminal block is the output for 1 10V or DSI if selected by software setup Note that most 1 10V HF fluorescent ballast control ...

Страница 6: ... for GND one pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The ...

Страница 7: ...vice Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This adjusts the maximum output that all other control sources can select ie if the Top Set is fully clockwise 100 selected by a control source will give 100 output If it is fully anti clockwise 100 selected by a control source will give 50 output This control ...

Страница 8: ... Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings specification Supply 230V 14 50 60Hz Single Phase at 60A or 230V 14 50 60Hz 3 Phase Y at 20A per phase Line Outputs 12 x Switched outputs at 5A per channel total device load 60A Control Outputs 12 x load control outputs selectable to 1 10V or DSI Protection 3 x 20A 6kA single pole thermal magnetic circui...

Отзывы: