![Philips 63059CM Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/philips/63059cm/63059cm_installation-and-operation-manual_282395015.webp)
Vision.net Ceiling Occupancy Sensor
Installation & Operation Guide
13
MANUAL CONFIGURATION
Using Programming Switches
There are two programming switches (buttons) on the Ceiling Occupancy Sensor which can be
used to Display and Modify the Sensor’s Settings. Programming Switch 2, the "Field" Button
(turns on the Blue LED when pressed) is used to select the Field you wish to display or
modify. Programming Switch 1, the "Setting" Button (turns on the Green LED when pressed)
is used to set the value of the selected Field. By using both buttons, the Sensor can be
manually configured for most applications.
To enter Manual Programming Mode:
Step 1. Unscrew Lens Cover on Ceiling
Sensor to access manual
programming buttons.
Step 2. Press and hold the Field Button for 3
seconds. After 3 seconds the Red
LED will turn on indicating the unit
is in the Manual Programming
Mode. Release the button.
To exit Manual Programming Mode:
There are three ways to exit the Programming
Mode.
•
Keep tapping the Field Button until
Ceiling Sensor exits Programming Mode.
•
Hold the Field Button for 3 seconds.
•
Stop tapping the buttons. The Ceiling
Sensor will exit the Programming Mode 1 minute after the last button press.
LED Display
When in the Programming Mode, the LEDs display the following information:
•
Red LED – Always On.
•
Blue LED – Blinks 1 to 6 times to indicate the Field being displayed or set (see Field/
Setting Table on next page).
•
Green LED – Blinks 1 to 9 times to indicate the present setting of the Field (see Field/
Setting Table on next page).
Programming
Switch 1 (Setting)
GREEN
Programming
Switch 2 (Field)
BLUE
Figure 4: Manual Programming Buttons
Содержание 63059CM