=0x06(PF)]
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter
Type = 0x01
,
Precision = 2
,
Scale = 0x06
,
Size = 1 Bytes
,
Meter
Value(PF)]
Example:
Scale = 0x06 (PF)
Precision = 2
Size = 1 (1 Byte of PF)
Meter Value 1 = 0x63(PF) (It means that the load power factor is 0.99)
3. Z-Wave’s Configuration
Configuration
Parameter
Function
Size
(Byte)
Value
Unit Default Description
1
Watt Meter
Report Period
2
0x0000
-
0x7FFF
5s
720
0: Disable Watt
Report
1~32767: 5s~ 45h
2
KWH Meter
Report Period
2
0x0000
-
0x7FFF
10min
6
0: Disable KWh
Report
1~32767:
10min~ 227days
3
Threshold of
current for Load
caution
2
10-1300 0.01A
1300
1300*0.01A
= 13A
4
Threshold of
KWh for Load
caution
2
1-10000 1KWh 10000
10000*1KWh
= 10000 KWh
5
Restore switch
state mode
1
0-2
1
0: Switch off
1: Last switch state
2: Switch on
6
Mode of Switch
Off function
1
0-1
1
0: Disable
1: Enable
7
LED indication
mode
1
1-3
1
1: Show switch state
2: Show night mode
3: One flash mode
8
Watt differential
mode
1
0-1
1
0 : Disable
1 : 5%
2: 10%
3: 15%
4: 10%
9
Switch status
report mode
1
0-1
1
0: Disable
1:Enable
3-1 Watt Meter Report Period:
If the setting is configured for 1hour (set value =720), PAN45 will report its
instant power consumption to Group1 node every 1 hour. The maximum inter-
val to report its instant power consumption is 45 hours
(5s*32767/3600=45hr). When the setting is 0, PAN45 will disable Watt auto
report function. The default value is 720.
3-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), PAN45 will report its Ac-
cumulated Power Consumption (KWh) to Group1 node every 1 hour. The
maximum interval to report its Accumulated Power Consumption (KWh) is
227.55 days (10min*32767/1440=227.55 days). When the setting is 0, PAN45
will disable KWH auto report function. The default value is 6.
3-3 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if
the setting value is 1300, when the load current of Relay1 over this value,
PAN45 will send current meter report to warn the Group1 node, the range of
the setting value is from 10 to 1300, and the default value is 1300.