Binary Switch Report Command:
Report OFF:

[Command Class Switch Binary, Switch Binary Report,

Value =0(0x00)]

Report ON:

[Command Class Switch Binary, Switch Binary Report,

Value = 255(0xFF)]

1-2 BASIC_SET / SWITCH_BINARY_SET

    Upon receipt of the following commands from a Z-Wave Controller, the load

attached to the Switch will turn on or off.

[Command Class Basic, Basic Set, Value = 1~99,255(0xFF)]

: the load

attached to the Switch turns on.

[Command Class Basic, Basic Set, Value = 0(0x00)]

: the load attached

to the Switch turns off.

[Command Class Switch Binary, Switch Binary Set, Value = 1~99,
(255)0xFF]

: the load attached to the Switch turns on.

[Command Class Switch Binary, Switch Binary Set, Value = 0(0x00)]

:

the load attached to the Switch turns off.

2.

Z-Wave’s Groups (Association Command Class Version 2)

The Switch can be set to send reports to associated Z-Wave devices.  It supports
one association group with one node support for Grouping 1. For group 1, the
Switch will report its latest status to Z-Wave Controller. 
Grouping   1   includes,   SWITCH_BINARY_REPORT,   METER_REPORT,
ALARM_REPORT.

2-1 Auto report to Grouping 1 (Maximum Node 5)

2-1-1 On/Off Event Report 

   When “on” or “off” state has been changed, it will send Binary Switch Report

to the node of Grouping 1. 

   

Binary Switch Report

ON:  

[Command Class Switch Binary, Switch Binary Report, Value

=255(0xFF)]

OFF:  

[Command Class Switch Binary, Switch Binary Report, Value

=0(0x00)]

2-1-2 Instant Power Consumption vary over 5% report

When the power consumption of load varies over 5%, it will send Meter report

to the nodes of Grouping 1.

Meter Report Command: 

[Command Class Meter

Meter Report

Rate Type = 0x01

Meter

Type = 0x01

Precision = 1

Scale = 0x02

Size = 4

Meter Value(W) ]

2-1-3 Overload alarm report
When PAN38 detects the current is more than 14.5A, it will send Alarm Report
to Group 1 node. 

The content of Alarm Report 

Alarm report command:

[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm
Level = 0xFF]

2-2 Response to Meter Get Command

   The Switch will report its (1) instant Power Consumption (Watt) or (2) accumu-

lated power consumption (KWH) or (3) AC load Voltage (V) or (4) AC load
current (I) (5) load power factor (PF) to Z-Wave Controller after receive the
Meter Get Command from Z-Wave Controller.

2-2-1 Instant Power Consumption (Watt) of Switch

    When receiving Meter Get Command, it will report Meter Report Command to

the node.

Содержание PAN38

Страница 1: ...to normal status Specification Operating Voltage 100V 240V 50Hz 60Hz Maximum Load Ampere 13A Resistive load PAN38 1 PAN38 2 PAN38 3 Maximum Load Ampere 10A Resistive load PAN38 4 Switzerland Socket Type Germany type PAN38 1 France type PAN38 2 UK type PAN38 3 Switzerland type PAN38 4 Range Minimum 40 m in door 100m outdoor line of sight Operating Temperature 0 C 40 C Frequency Range 868 40MHz 869 ...

Страница 2: ... putting it into use the body of Module will become a little bit hot of which phenomenon is normal Warning 1 Plug out to disconnect from power supply Do not plug in line 2 Do not exceed the max rating Warnung 1 Trennen Sie das Gerät von der Stromzuführung Verwenden Sie das Gerät nicht mit einem DIP Schalter 2 Achten Sie darauf dass die maximale Spannung niemals überschritten wird Warnung für zwisc...

Страница 3: ...ion Annotation No node ID The Z Wave Controller does not al locate a node ID to the Switch LED 2 second on 2 second off Add 1 Put your Z Wave controller into inclusion mode by following the instructions provided by the controller manufacturer 2 Pressing On Off button three times within 2 seconds will enter inclusion mode Remove 1 Put your Z Wave controller into exclusion mode by following the inst...

Страница 4: ...facing direct sunlight humid or dusty place 2 The suitable ambient temperature for the Switch is 0 C 40 C 3 Do not locate the Switch where exists combustible substances or any source of heat e g fires radiators boiler etc 4 After putting it into use the body of Switch will become a little bit hot of which phenomenon is normal Installation 1 Plug this On Off Switch into a wall outlet near the load ...

Страница 5: ...Auto report to Grouping 1 Maximum Node 5 2 1 1 On Off Event Report When on or off state has been changed it will send Binary Switch Report to the node of Grouping 1 Binary Switch Report ON Command Class Switch Binary Switch Binary Report Value 255 0xFF OFF Command Class Switch Binary Switch Binary Report Value 0 0x00 2 1 2 Instant Power Consumption vary over 5 report When the power consumption of ...

Страница 6: ... Meter Value 4 0xA3 KWh Accumulated power consumption KWh Meter Value 2 65536 Meter Value 3 256 Meter Value 4 800 35 KWh 2 2 3 Clearing accumulated power consumption Whenever re start counting the accumulated power consumption is needed you can use Meter Reset Command to clear it Meter Reset Command Command Class Meter Meter Reset 2 2 4 AC load Voltage V When receiving Meter Get Command it will re...

Страница 7: ...0 99 3 Z Wave s Configuration Configuration Parameter Function Size Byte Value Unit Default Description 1 Watt Meter 2 0x0000 5s 720 0 Disable Watt Report Period 0x7FFF Report 1 32767 5s 45h 2 KWH Meter Report Period 2 0x0000 0x7FFF 10min 6 0 Disable KWh Report 1 32767 10min 227days 3 Threshold of current for Load caution 2 10 1300 0 01A 1300 1300 0 01A 13A 4 Threshold of KWh for Load caution 2 1 ...

Страница 8: ...etting is LAST SWITCH STATE 3 6 Mode of switch off function When the mode of switch On Off is set to 0 any command of switch off will be disabled and the On Off function of include button will be disabled The default setting is enable mode When manual On Off function is disabled the RF com mand can only switch On but not Off This is useful function for keeping the de vice in switch on state 3 7 LE...

Страница 9: ...anted Security Class Meter 5 Highest granted Security Class Multi Channel Association 3 Highest granted Security Class Notification 8 Highest granted Security Class Powerlevel 1 Highest granted Security Class Version 3 Highest granted Security Class Socket Type Since the socket type for each country in Europe varies refer to the outline for each socket suited for each country as follows Germany ty...

Страница 10: ... used in accordance with the instructions may cause harmful inter ference to radio communications However there is no guarantee that interference will not occur in a particular in stallation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encour aged to try to correct the interference by one ...

Отзывы: