QP-10-IM21UL/Rev 12
between modules frame and the surface of the wall or roof.
7.
The minimum distance between two modules is at least (1.5 cm).
8.
Make sure that drain holes should not be blocked in any c a s e .
A-
Mounting using frame bolt Holes:
There are four holes on each long side
of the module’s frame used to
accommodate dedicated bolts intended for direct roof mounting, the modules
must be fastened to a support using the bolt holes in the frame (diameter of hole is
6 mm).
the module should be fastened with M8, flat washer, spring washer and hex
nut tighten to torque 11.65
–
16.9 ft.Ib (15.8
–
23 N.M). All fittings should be made of
stainless steel.
B-
Mounting Using Clamps:
1-
modules clamps should not contact
module’s glass or deform module’s
frame.
2-
Make sure to avoid shadowing from
using clamps.
3-
Make sure to avoid modifying
module’s
frame.
4-
Use 4 clamps on the long side of
each module.
5-
Applied torque is referring to the bolts that customer use, M8* L50 fully threaded:
(11.65
–
16.9 ft.lb: 15.8 - 23 N.m).
6-
Never use middle clamp instead of edge clamp.
Method B: Mounting using clamps is the only method evaluated by the testing and
certifying laboratory
The module is in compliance with this standard only when the module is mounted
in the manner specified by the mounting instructions. A module with exposed
conductive parts is considered to be in compliance with this standard only when it
is electrically grounded in accordance with the manufacturer’s instruction
s and the
requirements of the National Electrical Code ANSI/NFPA 70 (2014-2017