background image

BK-130 

6-1 

SECTION 6:  GUARD-GROUND-RETURN CONNECTIONS

 

 
 
The base of the High Voltage transformer contains a currentmeter feature useful in measurement of different 
current sources.  
 

 (

Refer To Figure 6-1

)  

 
1. 

Standard Mode (RTN)

 

 
(Use for liner testing) 

 

The standard configuration is set up to measure the current from the high potential side of the unit under 
test to ground. This configuration 

must

 be used if it is not possible to isolate the low voltage side of the 

object under test from ground. 
 
The low potential side of the unit under test is connected directly to ground.  The binding post Jumper 
Clip is installed between the “GND” and the “RETURN” posts on the base of the H. V. Transformer. 
 
This measures the output current flowing from the high voltage output through the unit under test to 
ground and the current meter then senses the return current from ground to the “RETURN” terminal of 
the high voltage transformer. 

 
2. 

Guard Mode

 

 
(Use for boom and chassis insulator testing) 

 
For test objects that can be fully isolated from ground it may be desirable to use the Guard Mode. In 
this mode only current passing through the test object will be displayed on the current meter. This will 
be especially important if very small currents are to be observed.  
 
In this mode the current path does not flow directly to ground from the low potential side of the unit 
under test, but flows through the currentmeter first and then to ground. 
 
The connection to be made is (1) connect the low potential side of the unit under test directly to the post 
marked RETURN and (2) connect the jumper clip between the GUARD and GND posts.  (

NOTE

:  The 

GND post is internally connected to the GROUND terminal.) 

 
 

 

 
 

CAUTION 

If the test specimen is not fully isolated from ground, the current meter will either not work, or not 

display accurate current readings, and this mode should not be used. 

Содержание BK130

Страница 1: ...130 USER S MANUAL AC DIELECTRIC TEST SET 600 SERIES Model Number BK130 36 Version 5 1 Phenix Technologies Inc 75 Speicher Drive Accident Maryland 21520 Copyright Phenix Technologies Inc Rev 2 9 2015 n...

Страница 2: ...BK 130 DANGER...

Страница 3: ...Test Equipment have been listed below for your reference Become familiar with your instrument before performing an actual test Know your work area check that all circuits are de energized and locked o...

Страница 4: ...CTRICAL 4 OPERATIONAL VERIFICATION GENERAL TEST 5 GROUND GUARD RETURN CONNECTIONS 6 CALIBRATION 7 TROUBLESHOOTING 8 MECHANICAL MAINTENANCE 9 CHECKING OIL PURITY SPECIFICATIONS 10 TRANSPORTING STORAGE...

Страница 5: ...ng Ambient Temperature 10 40 degrees C Output Termination 2 Polished Ball 36 kV 3 x 12 High Voltage Spinning 130 kV Metering Digital Output Voltmeter 3 Digit LCD Accuracy 0 8 of reading 2 of range Out...

Страница 6: ...care in removing shipping materials so as not to damage unit 2 Perform visual inspection to determine if unit was damaged during shipment If there are any signs of physical damage such as dents scratc...

Страница 7: ...BK 130 3 1 SECTION 3 CONTROLS AND INDICATORS Control Section FIGURE 3 1 TECHNOLOGIES PHENIX...

Страница 8: ...sed Reset Lamp off Emergency Off Button pulled up Voltage Control at Zero 11 Voltage Control Adjusts Output Voltage and must be set at zero to turn High Voltage on 12 Currentmeter Range Selector 13 Ou...

Страница 9: ...BK 130 3 3 CONTROLS AND INDICATORS FIGURE 3 2...

Страница 10: ...st be connected from Ground to Return When the Jumper Clip is tied from Ground to Guard GRD any stray leakage currents associated with Ground or Guard will bypass the Current Meter and will not be mea...

Страница 11: ...be sure the floor will be strong enough to support the unit If outdoor operation is to be used the site for the base must be capable of supporting the unit without any settling that would tilt the ass...

Страница 12: ...30kV position 4 Connect the RETURN terminal at the base of the high voltage transformer to the meter receptacle on the boom using a coaxial lead Included in the optional accessory package 5 Connect th...

Страница 13: ...BK 130 4 3 INITIAL SET UP ELECTRICAL Figure 4 1 TYPICAL TEST CONNECTIONS FOR CATEGORIES A B AERIAL DEVICES BONDING JUMPER BONDING JUMPER BONDING JUMPER EARTH or FACILITY GROUND HV TRANSFORMER CONTROLS...

Страница 14: ...selector switch on the front panel is in the 130kV position 4 Connect the RETURN terminal at the base of the high voltage transformer to the chassis of the truck using the supplied lead 5 Connect the...

Страница 15: ...Setup Electrical Figure 4 2 TYPICAL TEST CONNECTIONS FOR CATEGORY C AERIAL DEVICES BONDING JUMPER BONDING JUMPER BONDING JUMPER EARTH or FACILITY GROUND HV TRANSFORMER CONTROLS ISOLATION PADS UNDER TI...

Страница 16: ...ront panel is in the 130kV position 4 Connect the RETURN terminal at the base of the high voltage transformer to the chassis of the truck using the supplied lead 5 Connect the power connector on the h...

Страница 17: ...130 4 7 INITIAL SETUP ELECTRICAL Figure 4 3 TYPICAL TEST CONNECTIONS FOR CHASSIS INSULATORS EARTH or FACILITY GROUND HV TRANSFORMER CONTROLS ISOLATION PADS UNDER TIRES AND OUTRIGGERS CONTROLS CONTROL...

Страница 18: ...will engage External Interlock loop must be closed Emergency Off switch must be closed mushroom button up Overload Reset Lamp must be off Voltage Control at Zero Start and Transformer Power Circuit Br...

Страница 19: ...shorted output conditions Rated output currents are only available through a capacitive load of sufficient value Shorted current values should never exceed 50 of rated currents for the High Voltage Ta...

Страница 20: ...t will require Set the dial to a high enough value to preclude false failure indications If this value is not known it is recommended that the dial be left in a higher setting 6 Press the HV On switch...

Страница 21: ...ses the return current from ground to the RETURN terminal of the high voltage transformer 2 Guard Mode Use for boom and chassis insulator testing For test objects that can be fully isolated from groun...

Страница 22: ...BK 130 6 2 GUARD GROUND RETURN CONNECTIONS Figure 6 1...

Страница 23: ...ately rated High Voltage loads isolated from ground to the high voltage unit that will allow each full range current to be drawn at approximately 15 or higher output voltage This allows sufficient res...

Страница 24: ...inimum 1 current trip level should be approx 18mA When dial is set to maximum 11 trip level should be approx 198mA b Set the Overload Trip potentiometer R15 on the front panel to 1 and the Current Ran...

Страница 25: ...gency off has been pressed pull switch button up External interlock is open SX1 Voltage Control dial is not in zero start position Protection circuit Overload Trip is not Reset Transformer Power circu...

Страница 26: ...range switch or wiring Faulty Circuit on PCB1257 5 Voltmeter inoperable Faulty TX1 interconnect cable Meter damaged No high voltage present at output bushing Damaged or inoperative Measurement Divider...

Страница 27: ...oints for oil leakage If a leak is found retighten bolts to 5 ft lbs 3 Control Box Regulator Section At least once every year the control assembly should be removed for inspection of the regulator ass...

Страница 28: ...ASTM D 877 test procedure If the oil tests lower than this consult Phenix Technologies Service Department for recommendations Generally for small portable transformers with small oil volumes draining...

Страница 29: ...ir dielectric strengths of over 30 000 volts b Excellent Oxidation Stability Excellent oxidation stability and high resistance to sludging provide protection particularly where high temperatures are l...

Страница 30: ...hibitor Content ASTM D2668 w w 0 30 max Interfacial tension ASTM D971 dynes cm 40 min Density 15 C ASTM D1298 g ml 0 91 max Viscosity 100 C ASTM D445 cSt 3 0 max Viscosity 40 C ASTM D445 cSt 12 0 max...

Страница 31: ...ering to prevent damages during transport Prior to operation all insulating materials and bushings should be cleaned Protective caps should be in place on connectors 4 Optional cover for the transform...

Страница 32: ...D TR M K K K TB X Intensite Diode Transisteur Thyristor Borne Ouvert Ferme Contact de SYMBOLE ZU SCHEMA SYMBOLES POUR SCHEMA DE CIRCUIT CIRCUIT DIAGRAM SYMBOLS Variable Resisitor Resistor Lamp Indicat...

Страница 33: ...BK 130 13 1 SECTION 13 ELECTRICAL DIAGRAMS Drawing Number Description 9602130 120 V BK130 Electrical PCB 1257 9602132 220 240 V BK130 Electrical PCB 1257...

Страница 34: ...include the serial number of the unit as well as the part number of the replacement part When your purchase order is received at our office a representative of Phenix Technologies will contact you to...

Страница 35: ...ive for a recommendation Current prices may be obtained by contacting the Parts Ordering Department at Phenix Technologies PART NAME COMPUTER RECOMMENDED NUMBER QUANTITY LCD Meter KNS 3 Digit DMO 66T...

Страница 36: ...WR CBL 10 2 20FT INTERCONNECT 1 POWER CBL 220V 30110029 PWR CBL 14 2 20FT INTERCONNECT 1 R15 1761098 10k 2W LINEAR 01F2644 1 R15 DIAL 1355910 46 15 010 DIAL 30 0 011 1 R15 KNOB 1355101 26 15 61 3 KNOB...

Страница 37: ...066 13V TRANZORB 4 MOV3001 3 120 V 31107000 METAL OXIDE VARISTOR ASSY 1 MOV 3001 3 220 V 1606110 V275LA40 MOVISTOR 3 R3001 3002 1748410 200MEGS 1 6W ROX4ST SSX103 4 R3003 3004 1724400 0 5W 200K 1 2 R3...

Страница 38: ...er Reason for Return Cause of Defect If Phenix Technologies Inc deems return of the part appropriate it will then issue an Authorization for Return If return is not deemed advisable other inspection a...

Страница 39: ...s Manual are correct If there are concerns or comments as you have used this information Phenix Technologies appreciates any feedback Unit Serial Number Sect Page s Comment Please return to Phenix Te...

Отзывы: