Installation:
➢
Loosen the four cross-head screws in the lens and remove them upwards.
The holes for mounting the housing are then accessible, for dimensions see chapter
Alternative installation possible with the brackets supplied.
➢
Perform electrical connection on the circuit board in the lens as follows.
➢
Close the device again after setting the desired operating mode.
➢
Ensure that the sealing is clean and undamaged before assembly. (Ensure vapor tightness). Do not
use devices with damaged seals.
➢
Tighten the four cross-head screws of the lens crosswise in at least two rounds with a final torque of
approx. 1.5 Nm.
➢
Carry out a final functional test to ensure reliable signaling.
6.3
Electrical connection
S1
Selection of
operating
mode
Light intensity control
Flashing light
10
– 100%
Blinking / continuous light: 45
– 100%
X1
External control input
X2
Operating voltage
connection
DC:
AC:
Connection of
the line
Note:
Devices with DC voltage are equipped with reverse polarity protection. The function is guaranteed if the
polarity of the connections is reversed.
6.4 Setting the operating modes
S1
Operating mode
1
2
3
OFF OFF OFF
Flashing light
1 Hz
*
OFF OFF ON
Flashing light
0.75 Hz
OFF ON OFF
Continuous light
OFF ON ON
Blinking light
1 Hz
ON OFF OFF
Flashing light
2 Hz
ON OFF ON
Blinking light
2 Hz
ON ON OFF
Flashing light
0.1 Hz
ON ON ON
Flashing light
0.5 Hz
OFF OFF ON
S1
Color assignment
4
5
6
OFF
OFF OFF
Red
*
OFF ON
Blue
ON OFF
Green
ON ON
Yellow
*
Factory setting